Rockwell Automation Publication 193-UM015D-EN-P - February 2015
479
Parameter List
Appendix
B
Current Setup
continued
246
GFWarningLevel
C.GroundFaultWarnLimit
Ground Fault
Warning Level
UINT
2
100
2
500
200
Amps
247
GFFilter
C.GroundFaultFilterEn
Filter GF current
from %TCU
calculation
BOOL
1
1
0=Disable
1=Enable
0
248
GFMaxInhibit
C.GroundFaultMaxInhibitEn
Trip is inhibited
when GF exceeds
max value
BOOL
1
1
0=Disable
1=Enable
0
249
StallEnabledTime
C.StallEnabledTime
Stall Monitor and
Trip Delay
USINT
1
1
0
250
10
Second
s
250
StallTripLevel
C.StallTripLimit
Stall Trip Level
UINT
2
10
100
600
600
%FLA
251
JamInhibitTime
C.JamInhibitTime
Jam Detect Inhibit
Time
USINT
1
1
0
250
10
Second
s
252
JamTripDelay
C.JamTripDelay
Jam Detect Trip
Delay
USINT
1
10
1
250
50
Second
s
253
JamTripLevel
C.JamTripLimit
Jam Detect Trip
Level
UINT
2
1
50
600
250
%FLA
254
JamWarningLevel
C.JamWarnLimit
Jam Detect
Warning Level
UINT
2
1
50
600
150
%FLA
255
ULInhibitTime
C.UnderloadInhibitTime
Underload Inhibit
Time
USINT
1
1
0
250
10
Second
s
256
ULTripDelay
C.UnderloadTripDelay
Underload Trip
Delay
USINT
1
10
1
250
50
Second
s
257
ULTripLevel
C.UnderloadTripLimit
Underload Trip
Level
USINT
1
1
10
100
50
%FLA
258
ULWarningLevel
C.UnderloadWarnLimit
Underload
Warning Level
USINT
1
1
10
100
70
%FLA
259
CIInhibitTime
C.CurrentImbalanceInhibitTime
Current Imbalance
Inhibit Time
USINT
1
1
0
250
10
Second
s
260
CITripDelay
C.CurrentImbalanceTripDelay
Current Imbalance
Trip Delay
USINT
1
10
1
250
50
Second
s
261
CITripLevel
C.CurrentImbalanceTripLimit
Current Imbalance
Trip Level
USINT
1
1
10
100
35
%
262
CIWarningLevel
C.CurrentImbalanceWarnLimit
Current Imbalance
Warning Level
USINT
1
1
10
100
20
%
263
CTPrimary
C.CTPrimary
Current
Transformer
Primary Ratio
UINT
2
1
1
65535
5
264
CTSecondary
C.CTSecondary
Current
Transformer
Secondary Ratio
UINT
2
1
1
65535
5
265
UCInhibit Time
C.UnderCurrentInhibitTime
Under Current
Inhibit Time
USINT
1
1
0
250
10
Second
s
266
L1UCTripDelay
C.L1UnderCurrentTripDelay
L1 Under Current
Trip Delay
USINT
1
10
0
250
10
Second
s
267
L1UCTripLevel
C.L1UnderCurrentTripLimit
L1 Under Current
Trip Level
USINT
1
1
10
100
35
%
268
L1UCWarningLevel
C.L1UnderCurrentWarnLimit
L1 Under Current
Warning Level
USINT
1
1
10
100
40
%
269
L2UCTripDelay
C.L2UnderCurrentTripDelay
L2 Under Current
Trip Delay
USINT
1
10
0
250
10
Second
s
270
L2UCTripLevel
C.L2UnderCurrentTripLimit
L2 Under Current
Trip Level
USINT
1
1
10
100
35
%
271
L2UCWarningLevel
C.L2UnderCurrentWarnLimit
L2 Under Current
Warning Level
USINT
1
1
10
100
40
%
272
L3UCTripDelay
C.L3UnderCurrentTripDelay
L3 Under Current
Trip Delay
USINT
1
10
0
250
10
Second
s
273
L3UCTripLevel
C.L3UnderCurrentTripLimit
L3 Under Current
Trip Level
USINT
1
1
10
100
35
%
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...