Systemsoftware
2-16
System- and communication configuring D7-SYS - SIMADYN D
Edition 03.2001
The "SIMADYN D station" directory, available below the "Project name"
can now be selected after the project tree (project hierarchy) has been
displayed. The HWConfig program is now started by clicking twice on the
hardware symbol in the righthand side of the window.
Call-up the hardware catalog in the HWConfig window via the menu bar
Insert > Hardware components
.
For this project example, the
subrack
folder must be selected from the
SIMADYN D
directory. Select the required
SR6
subrack by double
clicking on it or per drag & drop, whereby the selected subrack must be
dragged, with the mouse key held, into the HWConfig window of the
SIMADYN D station.
Proceed in the same way for the required PM5 CPU module. It is located
in slot 1 in the subrack displayed.
The MS51 program memory module, automatically integrated in slot 1.1
in PM5 by HWConfig is now be removed. This is done by marking it and
removing it using the menu bar
Edit
>
Delete
. The MS5 program memory
module is now inserted, via the hardware catalog, into the directory
SIMADYN D
>
Sub-module
>
Program memory
>
MS5
per drag & drop
or clicking twice with the mouse.
The hardware can be parameterized differently than that pre-assigned by
double clicking on the CPU or on the memory module in the subrack.
Before HWConfig is terminated, the entered hardware configuration is
checked via the menu bar
Station
>
Check consistency
. HWConfig can
then be closed via
Station
>
Save
and
Station
>
Terminate
.
Now select the "Charts" directory, located under "Project name" after
displaying the complete project tree and select the menu item "
Insert
>
S7 software
>
CFC
".
Start the "CFC editor" program section by double clicking on the
CFC
symbol in the righthand section of the window.
Create the function block catalog from the menu bar using
View
>
Catalog
.
Drag the standard library FBSLIB on to a chart sheet of the CFC window
from the catalog. For example the function block types INT and R_I from
the control blocks and conversion blocks type classes.
By double clicking on the function block inputs/outputs or the function
block header, the pre-assignments can be changed in the CFC window
under
View
>
Sheet view
".
If the data format is the same, interconnections are created by a single
click on the output followed by a click on the required input.
NOTE
The sheet view can be increased (zoomed) using
View
>
Zoom
on the
menu bar.
HWConfig
Parameterizing the
hardware
SIMATIC Manager
CFC editor
Creating
interconnections