Chapter 8 20 Points RS485 type Models Instruction
210
More description and examples to see
Chapter5: Relay Ladder Logic Programming-MU (Modbus)
.
※
The max data length for Mode 1 and 3 is 25words. The max data length for Mode 4 is 400bits.
In FBD mode, program, edit and parameter display as shown blow;
Mode1
FBD display
Parameter display
Enable Input
→
←
Slaver ID
←
Register address
Parameter
→
←
Saving data address
More description and examples to see
Chapter6: FBD Block Diagram Programming-MU (Modbus) function
block
.
※
The max data length for Mode 1 and 3 is 25words. The max data length for Mode 4 is 400bits.
①
MU mode (1~5)
②
ID number of the target unit: range from 0 to127
The address of target register in that unit:
1) address is assigned to a constant, range from 0000 to ffff;
•
Just do the read/write function to the register with one data
length/address in mode 1 and 3.
•
Do the read/write function to the coil with one data
length/address in mode 4 and 5.
③
2) The address refers to the content of DR coil, and the value of coil
behind this one determines how many register or coil will be read or
write, see the next five pages for more information.
④
DR code, store sending/receiving data from this DR
⑤
MU code (MU01~MU0F)
PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor