Goodrive10 inverters Communication protocol
87
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
Communication
control command
2000H
0001H:forward running
W/R
0002H:reverse running
0003H:forward jogging
0004H:reverse jogging
0005H:stop
0006H:coast to stop (emergency stop)
0007H:fault reset
0008H:jogging stop
The address of
the
communication
setting value
2001H
Communication setting
frequency(0~Fmax)(unit: 0.01Hz))
W/R
2002H
PID reference, range(0~1000, 1000
corresponds to100.0% )
2003H
PID feedback, range(0~1000, 1000
corresponds to100.0% )
W/R
200AH
Virtual input terminal command , range:
0x000~0x1FF
W/R
200BH
Virtual input terminal command , range:
0x00~0x0F
W/R
200DH
AO output setting 1(-1000~1000, 1000
corresponds to 100.0%)
W/R
SW 1 of the
inverter
2100H
0001H:forward running
R
0002H:forward running
0003H:stop
0004H:fault
0005H: POFF state
SW 1 of the
inverter
2101H
Bit0: =0:bus voltage is not established
=1:bus voltage is established
R