DeviceNet • 127
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM 750
DeviceNet
5.6.2.1.8 Coupler configuration object (0x64):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Value
1
required
get
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
0x01
2
required
get
Max
instance
UINT
maximum instance number of an
object currently created in this
class level of device
0x01
Instance 1:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data
type
Description
1
specific
get/set
Bk_Module
No
USINT
module number: 0-Coupler, 1- first module,
2-2.module
2
specific
get/set
Bk_TableNo USINT
table number: 0 ... 256; not all existing
3
specific
get/set
Bk_Register
No
USINT
Register number: 0...255 for the Coupler
(0...63 for modules)
4
specific
get/set
Bk_Data
UINT
Register data , Status
5
specific
get
ProcessState
USINT
Coupler status: 0x01 module communication
error, 0x08: module diagnostic , 0x80 fieldbus
error
6
specific
get
DNS_i_Trm
nldia
(**)
UINT
Module status, 0x8000 to decode a message,
High Byte (Bit14...8): channel number, Low
Byte (Bit7..0) Module number
7
specific
get
CnfLen.
AnalogOut
UINT
number of I/O Bits for analog output data
words
8
specific
get
CnfLen.
AnalogInp
UINT
number of I/O Bits for analog input data
words
9
specific
get
CnfLen.
DigitalOut
UINT
number of I/O Bits for digital output data bits
10
specific
get
CnfLen.
DigitalInp
UINT
number of I/O Bits for digital input data bits
11
specific
get/set
BK_FAULT
_REACTIO
N
USINT
An enumerator used to specify fieldbus error
handling
0: stop local I/O cycles (default)
1: switch all outputs to 0
2: do nothing
3:switch all outputs to a predefined output
image
12
specific
get/set
BK_SEL_S
TORED_PO
LL_P_PAT
H
UINT
Non volatile power up value for the polled I/O
produced connection path. The attribute is
used to hold an enumerator for the assembly
path and the class and instance for the modu-
les object (discrete input point...) paths.Write
only instance values that are available for
Couplers present module configuration. (e.g.
do not use analog input points if only digital
modules are fixed to the Coupler.
0: bad value, path value not visible
1: analog and digital output data
2: only digital output data
3: only analog output data
4:analog and digital input data,status
5: only digital input data plus status
6: only analog input data plus status
7: analog and digital input data
8: only digital input data
9: only analog input data
13
specific
get/set
BK_SEL_S
TORED_PO
LL_C_PAT
H
UINT
Non volatile power up value for the polled I/O
consumed connection path. The attribute is
used to hold an enumerator for the assembly
path and the class and instance for modules
object (discrete input point ...) paths. Write