DeviceNet • 131
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM 750
DeviceNet
5.6.2.1.11
Analog Input Point Object (0x67):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Value
1
required
get
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
01
2
optional
get
Max
instance
UINT
maximum instance number of an
object currently created in this
class level of device
256
Description of the instances:
Instance ID
Description
1
reference to the first analog input point
2
reference to the next analog input point
...
255
reference to the last possible analog input point
Instance 1 to 255:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Value
1
dep. on kind
of connected
modules
get
AIPOBJ_
VALUE
Array of
Byte
Input data
aktual
input
Values
2
dep. on kind
of connected
modules
get
AIPOBJ_
VALUE
USINT
Input data length
Number
of Bytes
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read a DeviceNet Object attribute
value
0x10
Set_Attribute_Single
Used to modify a DeviceNet object attribute
value
5.6.2.1.12
Analog Output Point Object (0x68):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Value
1
required
get
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
01
2
optional
get
Max
instance
UINT
maximum instance number of an
object currently created in this
class level of device
256