134
• DeviceNet
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM 750
DeviceNet
Instance 1 to instance 255
Attribute ID
Used in buscoupler
Acces
Rule
Name
DeviceNet
data type
Description of attribute
Semantics of
values
1
Optional
Get/Set
FB_IN_
VAR
USINT
Input data
Actual input
data
Services:
Service code
Service name
Service description
0x0Eh
Get_Attribute_Single
Used to read an Object attribute value
0x10h
Set_Attribute_Single
Used to write an Object attribute value
5.6.2.2.5 Class 161 (0xA1) Input Fieldbus Variable USINT
PLC input byte 256 … 510
Max. instance: 255
5.6.2.2.6 Class 162 (0xA2) Input Fieldbus Variable USINT
PLC input byte 511 … 512
Max. instance: 2
5.6.2.2.7 Class 163 (0xA3) Output Fieldbus Variable USINT
Attribute ID
Used in buscoupler
Acces Rule
Name
DeviceNet data
type
Description of attribute
Semantics
of values
1
Required
Get
Revision
UINT
Revision of this object
0x01
2
Optional
Get
Max. instan-
ce
UINT
Max. instance number
of an object currently
created in this class
level of the device
255
Description for the object instance Ids
Instance ID
Description
1
Reference to the 1. PLC output byte
2
Reference to the 2. PLC output byte
…
255
Reference to the 255. PLC output byte
Instance 1 to instance 255:
Attribute
ID
Used in buscoupler
Acces Rule
Name
DeviceNet data
type
Description of attribute
Semantics
of values
1
Optional
Get
FB_OUT_VA
R
USINT
Output data
Actual
output
data
Services:
Service code
Service name
Service description
0x0Eh
Get_Attribute_Single
Used to read an Object attribute value