Module: Trip Control (TripControl)
Trip Control Module Signals (Outputs States)
Name
Description
TripCmd
Signal: Trip Command
Res TripCmd Cr
Signal: Resetting of the Counter: total number of trip commands
Ack TripCmd
Signal: Acknowledge Trip Command
Res Sum trip
Signal: Reset summation of the tripping currents
Pos
Signal: Circuit Breaker Position (0 = Indeterminate, 1 = OFF, 2 =
ON, 3 = Disturbed)
Ready
Signal: Circuit breaker is ready for operation.
Manual OFF
Signal: Circuit breaker was switched off manually.
Manual ON
Signal: Circuit breaker was switched on manually
Pos OFF
Signal: Circuit Breaker is in OFF-Position
Pos ON
Signal: Circuit Breaker is in ON-Position
Pos Indeterm
Signal: Circuit Breaker is in Indeterminate Position
Pos Disturb
Signal: Circuit Breaker Disturbed - Undefined Circuit Breaker
Position. The Position Indicators contradict themselves. After
expiring of a supervision timer the Position Indicators indicate that
the circuit breaker is in the ON and OFF-Position at the same time.
Trip Control Module Values
Value
Description
Default
Size
Menu path
TripCmd Cr
Counter: Total number of
trips of the switchgear
(circuit breaker, load
break switch…).
0
0 - 65535
[Operation
/Count and RevData
/CB]
EN MRU4 10/09
Page 235