4-39
Chapter 4
For parameter configuration
[Cb-01]
~
[Cb-35]
Analog input acquisition
Code/Name
Range (unit)
Initial
value
[A
i1
] t
er
m
in
al
Cb-01
Time constant of filter 1
~
500(ms)
16
Cb-03
Start value
0.00
~
100.00(%)
0.00
Cb-04
End value
0.00
~
100.00(%)
100.00
Cb-05
Start ratio
0.0
~
[Cb-06](%)
0.0
Cb-06
End ratio
[Cb-05]
~
100.0(%)
100.0
Cb-07
Start selection
00(Initial value)/
01(0%)
01
[
A
i2
] t
er
m
in
al
Cb-11
Time constant of filter 1
~
500(ms)
16
Cb-13
Start value
0.00
~
100.00(%)
0.00
Cb-14
End value
0.00
~
100.00(%)
100.00
Cb-15
Start ratio
0.0
~
[Cb-16](%)
0.0
Cb-16
End ratio
[Cb-15]
~
100.0(%)
100.0
Cb-17
Start selection
00(Initial value)/
01(0%)
01
[
A
i3
] t
er
m
in
al
Cb-21
Time constant of filter 1
~
500(ms)
16
Cb-22
Operation selection
00(Individual)/
01(Ai1/Ai2 add:
with inversion/
02(Ai1/Ai2 add:
without inversion)
00
Cb-23
Start value
-100.00
~
100.00(%)
-100.00
Cb-24
End value
-100.00
~
100.00(%)
100.00
Cb-25
Start ratio
-100.0
~
[Cb-26]
-100.0
Cb-26
End rattio
[Cb-25]
~
100.0
100.0
・
Regarding the adjustment method of the Analog input,
please refer to the chapter 3 example of I/O terminals
adjustment.
Analog input fine tuning
Code/Name
Range (unit)
Initial
value
Cb-30
[Ai1] Voltage/Current zero-bias
adjustment
-200.00
~
200.00(%)
0.00
Cb-31
[Ai1]
Voltage/Current gain
adjustment
-200.00
~
200.00(%)
100.00
Cb-32
[Ai2] Voltage/Current
zero-bias adjustment
-200.00
~
200.00(%)
0.00
Cb-33
[Ai2] Voltage/Current gain
adjustment
-200.00
~
200.00(%)
100.00
Cb-34
[Ai3] Voltage -10 bias
adjustment
-200.00
~
200.00(%)
0.00
Cb-35
[Ai3] Voltage gain adjustment
-200.00
~
200.00(%)
100.00
・
Regarding the adjustment method of the Analog input,
please refer to the chapter 3 example of I/O terminals
adjustment.
・
The thermistor adjustment, when recognizes an increase
in the adjustment value, reduces the resistor value.
[CA-40][Cb-41][CC-01]
~
[CC-17]
Thermistor error detection
Code/Name
Range (unit)
Initial
value
CA-40
Thermistor type
selection
00(Disable)/
01(PTC)/02(NTC)
00
Cb-41
Thermistor gain adjustment
0.0
~
1000.0
100.0
・
Set [CA-40] according to the connected thermistor in TH input
terminal.
・
When [CA-40]=01 or 02, with [bb-70] the error level is set. Refer to
[bb-70].
・
[Cb-41] thermistor gain adjustment, when the adjustment value is
raised the resistance value is lowered.
Output terminal settings
Code/Name
Range
(unit)
Initial
value
CC-01
Output terminal [11] function
Reference
<Intelligent
output
terminal
function
list>
002
CC-02
Output terminal [12] function
001
CC-03
Output terminal [13] function
035
CC-04
Output terminal [14] function
019
CC-05
Output terminal [15] function
030
CC-06
Output terminal [16] function
018
CC-07
Output terminal [AL] function
017
・
The functions for the output terminals 11
~
15,16A,AL are
assigned in [CC-01]
~
[CC-05],[CC-06],[CC-07].
Output terminal NO/NC settings
Code/Name
Range
(unit)
Initial
value
CC-11
Output terminal [11] active state
00(Normally
open: NO)/
01(Normally
closed: NC)
00
CC-12
Output terminal [12] active state
00
CC-13
Output terminal [13] active state
00
CC-14
Output terminal [14] active state
00
CC-15
Output terminal [15] active state
00
CC-16
Output terminal [16] active state
00
CC-17
Output terminal [AL] active state
01
・
The functions for the Intelligent output terminals 11
~
15,16,AL are assigned in [CC-11]
~
[CC-15], [CC-16],
[CC-17].
Summary of Contents for P1-00041HFEF
Page 6: ...0 5 Contents Contents Memo ...
Page 42: ...2 26 Chapter 2 Installation and Wiring Memo ...
Page 129: ...Index Index 3 memo ...
Page 130: ...Index Index 4 memo ...