26
05.17
Selection of
wave-by-wave
current limit
LED bit
:
In acceleration
0
:
invalid
1
:
valid
LED ten bits
:
In deceleration
0
:
invalid
1
:
valid
LED hundred-bits: In constant speed
0
:
invalid
1
:
valid
LED Thousand bits:Reserved
000
~
111
011
×
05.18
Output phase lost
protection detection
coefficient
When the ratio of the maximum value to the minimum value in the
three-phase output current is greater than this coefficient and the
duration exceeds 6 seconds, the frequency inverter reports the output
current imbalance fault EPLI
;
; Output open-phase protection is invalid
when 05.18=0.00.
0.00
~
20.00
2.00
○
05.19
Frequency drop
coefficient of
instantaneous power
failure
Set the instantaneous power-down frequency drop factor
0: the instantaneous
stop function is invalid
1
~
9999
0
○
05.20
Instantaneous power
down loss frequency
reduction voltage
point
Instantaneous power down loss frequency reduction voltage point
220V:180
~
330V
250V
380V:300
~
550V
450V
Model
setting
×
06 group: communication parameters
Function
code
Name
Setting range
Minimum unit
Factory
setting
Change
06.00
Local Address
Set the local address, 0 is the broadcast address.
0
~
247
1
×
06.01
MODBUS
communication
configuration
LED bit
:
baud rate selection
0
:
9600BPS
1
:
19200BPS
2
:
38400BPS
LED ten bits
:
data format
0
:
no parity
1
:
even parity check
2
:
Odd Parity Check
LED hundred bits:Communication response mode
0
:
normal response
1
:
Only respond to the slave address
2
:
no response
3
:
The slave machine does not respond to the free stop instruction of
the host machine in broadcast mode
LED thousand bits:Reserved
0000
~
0322
0000
×
06.02
communication
timeout check-out time
If the machine does not receive the correct data signal within the
time interval defined by this function code, then the machine thinks
that the communication has failed, and the frequency inverter will
decide whether to protect or maintain the current operation
according to the setting of the communication failure action mode;
When this value is set to 0.0, RS485 communication timeout
detection is not performed.
0.1
~
100.0s
10.0s
×
06.03
local machine
response delay time
This function code defines the intermediate time interval between
receiving the data frame of the inverter and sending the response
data frame to the upper computer. If the response time is less than
the system processing time, the system processing time shall
prevail.
0
~
200ms
5ms
×
06.04
Proportional linkage
coefficient
This function code is used to set the weight coefficient of frequency
instruction received by inverter as slave through RS485 interface,
and the actual operating frequency of this machine is equal to the
value of this function code multiplied by the value of frequency
setting instruction received through RS485 interface. In the linkage
control, this function code can set the ratio of operating frequency of
multiple inverters.
0.01
~
10.00
1.00
○
06.05
Multi-vendor
agreement selection
(reserved)
Reserved
0
~
3
0
×