Chapter 4: Using the Command Line Interface
156
Sensor type
Description
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
lineFrequency
Line frequency sensor
Note: If the requested sensor type is not supported, the "Sensor is not available" message is displayed.
•
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the specified threshold for a specific outlet sensor.
disable
Disables the specified threshold for a specific outlet sensor.
A numeric value
Sets a value for the specified threshold of a specific outlet sensor and enables this
threshold at the same time.
•
<hy_value> is a numeric value that is assigned to the hysteresis for the specified outlet sensor. Refer to
"To De-assert"
and Deassertion Hysteresis
in the PDU With RackLink User Manual at
www.middleatlantic.com/resources/power-downloads.aspx.
•
<as_value> is a number in samples that is assigned to the assertion timeout for the specified outlet sensor. Refer to
Configuring An Assertion Timeout
in
the PDU With RackLink User Manual at
www.middleatlantic.com/resources/power-downloads.aspx.
Commands for Inlet Sensors
A sensor configuration command for inlets begins with
sensor inlet
.
You can configure various inlet sensor threshold settings at a time by combining multiple commands. See
Set the Upper Critical threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> upperWarning <option>