Chapter 4: Using the Command Line Interface
156
Set the assertion timeout for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> assertionTimeout <as_value>
Variables:
•
<n> is the number of the overcurrent protector that you want to configure.
•
<sensor type> is one of the following sensor types:
Sensor type
Description
current
Current sensor
Note: If the requested sensor type is not supported, the "Sensor is not available" message is displayed.
•
<option> is one of the options:
enable
,
disable
or a numeric value.
Option
Description
enable
Enables the specified threshold for the overcurrent protector sensor.
disable
Disables the specified threshold for the overcurrent protector sensor.
A numeric value
Sets a value for the specified threshold of the overcurrent protector sensor and enables this
threshold at the same time.
•
<hy_value> is a numeric value that is assigned to the hysteresis for the specified overcurrent protector sensor. Refer to
"To De-assert" and Deassertion Hysteresis
in the PDU With RackLink User Manual at
www.middleatlantic.com/resources/power-downloads.aspx.
•
<as_value> is a number in samples that is assigned to the assertion timeout for the specified overcurrent protector
sensor. Refer to
Configuring An Assertion Timeout
in
the PDU With RackLink User Manual at
www.middleatlantic.com/resources/power-downloads.aspx.
Commands for Environmental Sensors
A sensor threshold configuration command for environmental sensors begins with
sensor externalsensor
.
You can configure various environmental sensor threshold settings at a time by combining multiple commands. See
(on page 122).
Set the Upper Critical threshold for an environmental sensor:
config:#
sensor externalsensor <n> <sensor type> upperCritical <option>