Chapter 4: Using the Command Line Interface
156
Overcurrent Protector Information
This command is only available for models with overcurrent protectors for protecting outlets.
This command syntax shows the overcurrent protector information, such as a circuit breaker or a fuse.
#
show ocp <n>
To show detailed information, add the parameter "details" to the end of the command.
#
show ocp <n>
details
Variables:
•
<n> is one of the options:
all
, or a number.
Option
Description
all
-- OR --
[blank]
Displays the information for all overcurrent protectors.
A specific overcurrent
protector number
Displays the information for the specified overcurrent protector only.
Displayed information:
•
Without the parameter "details," only the overcurrent protector status and name are displayed.
•
With the parameter "details," more overcurrent protector information is displayed in addition to status, such as the
rating and RMS current value.
Date and Time Settings
This command shows the current date and time settings on the PDU.
#
show time
To show detailed information, add the parameter "details" to the end of the command.
#
show time
details
Default Measurement Units
This command shows the default measurement units applied to the PDU web and CLI interfaces across all users,
especially those users authenticated through remote authentication servers.
#
show user defaultPreferences