Chapter 4: Using the Command Line Interface
156
Displayed information:
•
Without the parameter "details," only the reading, threshold, deassertion hysteresis and assertion timeout settings of
the specified environmental sensor are displayed.
•
With the parameter "details," more sensor information is displayed, including resolution and range.
Note: For a state sensor, the threshold-related and accuracy-related data is NOT available.
Environmental Sensor Default Thresholds
This command syntax shows a certain sensor type's default thresholds, which are the initial thresholds applying to the
specified type of sensor.
#
show defaultThresholds <sensor type>
To show detailed information, add the parameter "details" to the end of the command.
#
show defaultThresholds <sensor type>
details
Variables:
•
<sensor type> is one of the following numeric sensor types:
Sensor types
Description
absoluteHumidity
Absolute humidity sensors
relativeHumidity
Relative humidity sensors
temperature
Temperature sensors
airPressure
Air pressure sensors
airFlow
Air flow sensors
vibration
Vibration sensors
all
-- OR --
[blank]
All of the above numeric sensors
Displayed information:
•
Without the parameter "details," only the default upper and lower thresholds, deassertion hysteresis and assertion
timeout settings of the specified sensor type are displayed.
•
With the parameter "details," the threshold range is displayed in addition to default thresholds settings.