If the system-level diagnostics
tests…
Then…
Were completed without any
failures
a. Clear the status logs:
sldiag device clearstatus
b. Verify that the log was cleared:
sldiag device status
The following default response is displayed:
SLDIAG: No log messages are present.
c. Exit Maintenance mode on both controllers:
halt
The system displays the LOADER prompt.
You must exit Maintenance mode on both
controllers before proceeding any further.
d. Enter the following command on both controllers at the LOADER
prompt:
bye
e. Return the controller to normal operation:
If your system is running
ONTAP…
Then…
With two nodes in the cluster
Issue these commands:
node::> cluster ha modify
-configured true``node::> storage failover modify
-node node0 -enabled true
With more than two nodes in the
cluster
Issue this command:
node::> storage failover modify
-node node0 -enabled true
In a two-node MetroCluster
configuration
Proceed to the next step. The MetroCluster switchback procedure is
done in the next task in the replacement process.
In a stand-alone configuration
You have no further steps in this particular task.
You have completed system-level diagnostics.
240