Manual – DFD11B DeviceNet Fieldbus Interface
6
The Common Industrial Protocol (CIP)
DeviceNet Characteristics
Instance 3 ... 37
Instances 3 ... 37 give access to the fieldbus parameters.
Fieldbus
parameters
MOVIDRIVE
®
B
Supported ser-
vices
Attribute Access
Name
Data type
Default value
[hex]
Description
1
Set/Get
Parameter
UINT
Parameter that is to be read or writ-
ten see table fieldbus parameter
MOVIDRIVE
®
B
2
Get
Link Path
Size
USINT
00
No link is specified.
3
Get
Link Path
Packed
EPATH
00
Not used
4
Get
Descriptor
WORD
0000
Read/write parameter
5
Get
Data Type
EPATH
00C8
UDINT
6
Get
Data Size
USINT
04
Data length in bytes
Instance
Access
Group
Name
Meaning
3
Get
Device
parame-
ters
Device identification
Part number device
4
Get/Set
Control source
Control signal source
5
Get/Set
Setpoint source
Setpoint source
6
Get
PD configuration
Process data configuration
7
Get/Set
Setp.descr.PO1
Process output data assignment for PD1
8
Get
Setp.descr.PO2
Process output data assignment for PD2
9
Get/Set
Setp.descr.PO3
Process output data assignment for PD3
10
Get
Act.v.descr. PI1
Process input data assignment for PD1
11
Get/Set
Act.v.descr. PI2
Process input data assignment for PD2
12
Get
Act.v.descr. PI3
Process input data assignment for PD3
13
Get/Set
PO Data Enable
Enable process data
14
Get
Timeout response
Timeout response
15
Get
Fieldbus type
Fieldbus type
16
Get
Baud rate
Baud rate via DIP switches
17
Get
Station address
MAC-ID via DIP switches
18 ... 27
Get
PO moni-
tor
PO1 setpoint ...
PO10 setpoint
Monitor of the
Process output data words
28 ... 37
Get
PI monitor
PI1 actual value ...
PI10 actual value
Monitor of the
Process input data words
NOTE
The data format for these instances deviates from the SEW fieldbus profile to meet the
DeviceNet specification.
Service Code [hex]
Service Name
Class
Instance
0E
Get_Attribute_Single
X
X
10
Set_Attribute_Single
-
X
0
0
I