5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
102
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
136 -
143
(88h -
8Fh)
Sensor para-
meter data
G/S
ENUM
USINT
Contains the sensor-specific parameter data
of the channels 1 to 8 of the analog input
module.
Only those channels are supported that are
defined in attribute 111, "Number of
supported channels".
Attribute 136 contains the data for channel
1, attribute 143 for channel 8.
ENUM USINT:
Element:
0:Pt100, -200...850 °C
1:Pt100, -200...150 °C
2:Ni100, -60...250 °C
3:Ni100, -60...150 °C
4:Pt200, -200...850 °C
5:Pt200, -200...150 °C
6:Pt500, -200...850 °C
7:Pt500, -200...150 °C
8:Pt1000, -200...850 °C
9:Pt1000, -200...150 °C
10:Ni1000, -60...250 °C
11:Ni1000, -60...150 °C
12:resistance: 0...100
Ω
13:resistance: 0...200
Ω
14:resistance: 0...400
Ω
15:resistance: 0...1000
Ω
16 to 255: reserved
Table 53:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type