5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
110
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
A
Depend on the
selected opera-
ting mode (CNT/
MSRM) and are
not supported in
the other opera-
ting mode. Please
refer to Attribute
No. 113 BASIC
MODE.
122
(7Ah)
CNT
hysteresis
A
G/S
USINT
Defines the hysteresis, meaning the diffe-
rential threshold value.
Hysteresis
123
(7Bh)
CNT pulse dura-
tion
A
G/S
USINT
Defines the pulse duration.
Pulse duration [n * 2 ms]
124
(7Ch)
MSRM pulses per
revolution
A
G/S
UINT
Defines the number of pulses per revolu-
tion.
Pulses per revolution
125
(7Dh)
Fault value DO1
G/S
BOOL
Defines the substitute value of the digital
output DO1.
Fault value DO1:
FALSE: 0 = off, 0V
TRUE: 1 = on, 24V
126
(7Eh)
Diagnostic DO1
G/S
BOOL
Defines if the diagnostic data of the DO1 are
transmitted to the gateway.
Diagnostic DO1:
– FALSE: on
Diagnostic data of the DO1 are being
transmitted
– TRUE: off
Diagnostic data of the DO1 are not being
transmitted
127
(7Fh)
Function DO1
A
G/S
ENUM
USINT
Defines the function of the output DO1.
Function DO1:
0: output
1: CNT:
on when count value
≧
reference value
2: CNT:
on when count value
≦
reference value
3: CNT:
pulse when count value = reference value
4: MSRM: outside of limit
5: MSRM: below lower limit
6: MSRM: above upper limit
7 to 255: reserved
Table 55:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description