33/ 53
Parameter Name
Options/
Value Range
Description
fuel station switches off normally without flushing.
The “Flush Filter” process is only suggested by the system if
previously a defueling process happened, and effectively a
minimum amount of fuel has been aspirated!
Burst Protection
"DISABLED",
"Low sensitivity"
"Medium
sensitivity"
["High sensitivity"]
"Ultra-sensitive"
Protection system to avoid the bursting of fuel tanks if the
tank overflow has not been opened, or even if, for
example, a bag tank is falsely refueled with a program that
only analyses the flowback line. In both cases, an
impermissible high pressure will be created in the tank
system, which may lead to a tank bursting.
If this function is active (i.e. not "DISABLED"), the current
fuel flow is compared with an automatically determined
mean value. If the current flow rate drops too much,
refueling is aborted with the error message "Overpressure
STOPPED!".
Fill-line break
"Checking OFF"
["Checking ON"]
Automatic shut-off when refueling hose unintentionally
"falls off"/disconnects during filling.
In this case, the flow will rise abruptly, this circumstance is
evaluated as a shutdown criterion.
If this function is activated, the refueling process is
interrupted with the error message:
"Fill-line disconnected!".
Values in brackets [] indicate the standard values.