IntelliTouch i-Link Protocol Interface Adapter User’s Guide
AUXxx:
Auxiliary Circuit Control
Control/Query/Toggle available Auxiliary, Feature, or Macro Circuits.
Request State:
Query:
#AUXxx ?<cr>
Response:
!00 AUXxx = x<cr>
(RSPFMT = 0)
!00 x<cr>
(RSPFMT = 1)
Where x is 1 or 0, and 1 indicates ON, 0 indicates OFF
Set State:
Command:
#AUXxx = x<cr>
Where x is 1 or 0, and 1 indicates ON, 0 indicates OFF
Response:
!00 AUXxx = x<cr>
(RSPFMT = 0)
!00 x<cr>
(RSPFMT = 1)
Where x is 1 or 0, and 1 indicates ON, 0 indicates OFF
Toggle State:
Toggle:
#AUXxx <cr>
Response:
!00 AUXxx = x<cr>
(RSPFMT = 0)
!00 x<cr>
(RSPFMT = 1)
Where x is 1 or 0, and 1 indicates ON, 0 indicates OFF
Where ‘xx’ is 1 through 8, and 11 through 50.
AUX1 through AUX8 control up to eight (8) auxiliary circuits in the main power center.
This is also where the Spa & Pump (pool) circuits reside.
AUX11 through AUX20 Control up to ten (10) auxiliary circuits in the second power
center.
AUX21 through AUX30 Control up to ten (10) auxiliary circuits in the third power center.
AUX31 through AUX40 Control up to ten (10) auxiliary circuits in the third power center
AUX41 through AUX50 Control up to ten (10) feature or macro that exist in most
systems.
Note:
The adapter will not verify the existence of a given circuit. For example, if a
command is given for AUX22, and no such circuit exists in the system, no indication is
given. The state and status will appear normal. It is the installer/operators responsibility
to insure circuits exist.
AUXxx:
Dimmer Circuit Control
AUXxx+:
AUXxx-:
Control/Query/Toggle available Dimmer.
Request State:
Query:
#AUXxx ?<cr>
Response:
!00 AUXxx = x xx%<cr>
(RSPFMT = 0)
Where x is 1 or 0, and 1 indicates ON, 0 indicates OFF
If the Dimmer is ON, the xx% will follow indicating the level. 30%, 40%, 50%,
60%, 70%, 80%, 90% and 100% are all valid.
!00 xxx<cr>
(RSPFMT = 1)
Where xxx is 0, to indicates OFF, and is a value to indicate level
If ON. The Value is 128 + %. (i.e. 30% = 128 + 30 = 158)
7