Holding registers
Expansion I/O registers
Adding expansion I/O modules to the 415U will automatically add
the I/O from the 115S modules to the internal 415U-2 I/O store. To
calculate the register location in the I/O store, find the address of
the I/O point in the tables in this appendix, and then add the offset.
The offset is the Modbus address, multiplied by 20.
Examples:
•
Digital input #1 on an 115S-11 with address 5 would be: (5x20)
+10001 = 10101
•
Digital output #2 on an 115S-11 with address 6 would be: (6x20)
+2 = 122
•
Analog input #3 on an 115S-12 with address 3 would be: (3x20)
+30003 = 30063.
•
Analog output #8 on an 115S-13 with address # 7 would be:
(7x20) + 40007 = 40147
I/O store for 115S-11 expansion I/O modules
I/O store
Description
0001 + Offset
0016 + Offset
DIO outputs 1–16
10001 + Offset
10016 + Offset
DIO inputs 1–16
10019 + Offset
Modbus Comms Fail indication for this 115S module
10020 + Offset
Modbus Comms Fail indication (inverse) for this 115S module
30001 + Offset
30004 + Offset
115S-11 pulsed input rate 1–4
30005 + Offset
30012 + Offset
115S-11 pulsed input count
30017 + Offset
Modbus Error counter for this 115S module
30018 + Offset
Modbus Last Error code for this 115S module (see “Expansion I/O error registers” on page 61.)
30019 + Offset
Modbus Lost Link counter for this 115S module
30020 + Offset
Module type (0x0101) = 257 / error status
40009 + Offset
40016 + Offset
Pulsed output target 1–8 (1 register per pulsed output)
I/O store for 115S-12 expansion I/O modules
I/O store
Description
0001 + Offset
0008 + Offset
DIO outputs 1–8
10001 + Offset
10008 + Offset
DIO Inputs 1–8
10019 + Offset
Modbus Error indication for 115S module
10020 + Offset
Detected indication for this 115S module
30001 + Offset
30008 + Offset
Inputs AIN 1–AIN 8
30017 + Offset
Modbus Error counter for this 115S module
30018 + Offset
Modbus Last Error code for this 115S module (see “Expansion I/O error registers” on
page 61
)
30019 + Offset
Modbus Lost Link counter for this 115S module
30020 + Offset
Module type (0x0201) = 513 / error status
40009 + Offset
40016 + Offset
Pulsed output target 1–8 (1 register per output)