Version 1.0 09/08/2017
http://www.inorea.com
52
Code
Parameter name
Setting range
Factory default
Change
F1.13
AI2 lower limit
0.00V to F1.15
0.00V
☆
F1.14
AI2 lower limit setting
-100.0% to 100.0%
0.0%
☆
F1.15
AI2 upper limit
F1.13 to 10.00V
10.00V
☆
F1.16
AI2 upper limit setting
-100.0% to 100.0%
100.0%
☆
F1.17
Filter time of AI2 input
0.00s to 10.00s
0.10s
☆
AI2 function setting is similar with the way of AI1.
F1.18
Times of switching quantity filtering
1 to 10
5
☆
Set sampling filter time of DI1 to DI4 terminals. For the application that input terminals are vulnerable to interference and
cause the accidental operation, you can increase this parameter so as to enhance the anti-interference ability. However, the
increase of filter time will cause DI terminal slow response.
F1.19
DI terminal mode selection
0x000 to 0x1FF
000
★
This function code is used to set the polarity of the input terminals. When the bit is set to 0, the
polarity of input terminal is positive; when the bit is set to 1, the polarity of input terminal is
negative.
Bit0
Bit1
Bit2
Bit3
Bit4
DI1
DI2
DI3
DI4
DI5
Bit5
Bit6
Bit7
Bit8
Bit9
Reserved
Reserved
Reserved
Reserved
Reserved
5-2-3.
F2 Group - Output terminals group
Code
Parameter name
Setting range
Factory default
Change
F2.00
MO1 output selection
0 to 10
1
☆
F2.01
Reserved
-
F2.02
Reserved
-
F2.03
Relay output selection
1
☆
Set
value
Function
Description
0
No output
The function of Output terminal is
disabled.
1
Motor is running
forward
Inverter Run Forward: when the inverter
runs forward, if the frequency output
exists, ON signal will output.
2
Motor is running
reverse
Inverter Run Reverse: when the inverter
runs reverse, if the frequency output exists,
ON signal will output.
3
Fault output
Fault Output: When the inverter occurs
failure, and outputs ON signal.
4
Frequency level
detection FDT output
For the frequency level detection FDT
arrival, please refer to refer to the details
on the function code F7.10, F7.11.
5
Frequency arrival
For the frequency arrival, please refer to
the details on the function code F7.12.
6
Zero speed running
Zero Speed Running: if the output
frequency and the setting frequency of
inverter are simultaneously zero, ON signal
will output.