206
7-2. Troubleshooting
Total-check error code
Correct the program according to the
following table.
Error
code
E1
E2
E3
E4
E5
E8
Name of error
Syntax error
(SYNTAX)
Duplicated
output error
(DUP USE)
Not paired error
(PAIR)
System register
parameter error
(MISMATCH)
Program area
error
(PRG AREA)
Operand error
(OPR COMBI)
Description
Instruction is incorrectly
programmed.
Two or more OT
instructions are programmed
using same relay.
One of the instructions,
which must be paired, is
missing (e.g., JP and LBL).
The paired instruction sets
may have been programmed
in the incorrect order (e.g.,
MC and MCE).
The operand for the
instruction is out of the
range set in the system
register.
The instruction has been
programmed in the incorrect
position (e.g., INT and IRET
instructions are programmed
at the address before the
ED instruction).
Incorrect operand has been
entered for the instruction.
Steps to take
Input the instruction correctly,
referring to the description for
that instruction.
Correct the program so that
one relay is not used for two
or more OT instructions.
Program the missing
instruction.
Program the instruction sets
in the proper order, referring
to the description of the
instruction.
Check the system register
parameter using a FP
Programmer
II
(OP50) or
NPST-GR Software
(1. SYSTEM REGISTER in
the PLC CONFIGURATION).
Program the instruction in
the proper position, referring
to the description of the
instruction.
Program the instruction using
the correct operand, referring
to the description of the
instruction.
Set the mode selector of the programmable
controller from PROG. to RUN.