Modbus Data Base
Publication PUB091-003-00_0119
49 of 76
Location
(Reg/Bit)
R/W
Data
Range
5
-
R/W
Actuator Digital Control
0-3
0 = stop,
1 = close
2 = open
3 = ESD
6
-
R/W
Actuator Position DV (desired value)
0-3E8 hex
(0.0 – 100.0%)
26-
31
-
R/W
Actuator Tag name
12 bytes
ASCII char
Note:
①
Pressure instead of Torque in SI Pro and EH Pro
.
The following Data Logger information is also accessed by function code 03. Torque values are in the
range 0 – 120%. The registers are updated with new data a short period after the actuator stops
moving provided the actuator selector is in remote. The values may not contain the updated
information for up to 2 minutes.
Location
(Reg/Bit)
R/W
Data
Range
32
-
RO
Close Torque set
0-78 hex
33
-
RO
Open Torque set
0-78 hex
34
-
RO
Torque at 0% - open direction
0-78 hex
35
-
RO
Torque at 10% - open direction
0-78 hex
36
-
RO
Torque at 20% - open direction
0-78 hex
37
-
RO
Torque at 30% - open direction
0-78 hex
38
-
RO
Torque at 40% - open direction
0-78 hex
39
-
RO
Torque at 50% - open direction
0-78 hex
40
-
RO
Torque at 60% - open direction
0-78 hex
41
-
RO
Torque at 70% - open direction
0-78 hex
42
-
RO
Torque at 80% - open direction
0-78 hex
43
-
RO
Torque at 90% - open direction
0-78 hex
44
-
RO
Torque at 100% - open direction
0-78 hex
45
-
RO
Torque at 0% - close direction
0-78 hex
46
-
RO
Torque at 10% - close direction
0-78 hex
47
-
RO
Torque at 20% - close direction
0-78 hex
48
-
RO
Torque at 30% - close direction
0-78 hex
49
-
RO
Torque at 40% - close direction
0-78 hex
50
-
RO
Torque at 50% - close direction
0-78 hex
51
-
RO
Torque at 60% - close direction
0-78 hex
52
-
RO
Torque at 70% - close direction
0-78 hex
53
-
RO
Torque at 80% - close direction
0-78 hex
54
-
RO
Torque at 90% - close direction
0-78 hex
55
-
RO
Torque at 100% - close direction
0-78 hex
56
-
RO
Close Contactor counts low order
0-FFFF hex
57
-
RO
Close Contactor counts high order
0-FFFF hex
58
-
RO
Open Contactor counts low order
0-FFFF hex
59
-
RO
Open Contactor counts high order
0-FFFF hex