7PG2113/4/5/6 Data Communications
©2010 Siemens Protection Devices Limited
Chapter 4 Page 15 of 38
Section 4: Modbus Definitions
4.1
Introduction
This section describes the MODBUS-RTU protocol implementation in the relays. This protocol is used for
communication with a suitable control system.
This protocol can be set to use the RS485 port. The relay can communicate simultaneously on all ports
regardless of protocol used.
Each relay must be given an address to enable communication and can be set by the
Communication
Interface:Relay Address.
Definitions with shaded area are not available on all relay models.
Coils (Read Write Binary values)
Address Description
00001 Binary
Output
1
00002 Binary
Output
2
00003 Binary
Output
3
00004 Binary
Output
4
00005 Binary
Output
5
00006
Binary Output 6
00007
Binary Output 7
00008
Binary Output 8
00100
LED Reset (Write only location)
00101
Settings Group 1
00102
Settings Group 2
00103
Settings Group 3
00104
Settings Group 4
00109 CB
1
00110
CB 1 Trip & Reclose
00111
CB 1 Trip & Lockout
00112 Auto-reclose
on/off
00113
Hot Line Working on/off
00114 E/F
off/on
00115
00116
Inst Protection off/on
00118
Reset CB Total Trip Count
00119
Reset CB Delta Trip Count
00120
Reset CB Count To AR Block
00121
Reset CB Frequent Ops Count
00123
Reset I^2t CB Wear