100 Parameters
Shows the status of the adaptive program.
See section
-
0000h…FFFFh
Adaptive program status.
1 = 1
Shows the number of the active state of the
sequence program part of the adaptive program
(AP). If adaptive programming is not running, or
it does not contain a sequence program, the
parameter is zero.
0…20
1 = 1
10
Configuration of digital inputs and relay outputs.
Shows the status of digital inputs DI1…DI6. Bits
0…5 reflect the delayed status of DI1…DI6.
Example:
0000000000010011b = DI5, DI2 and DI1
are on, DI3, DI4 and DI6 are off.
This word is updated only after a 2 ms
activation/deactivation delay. When the value of
a digital input changes, it must remain the same
in two consecutive samples, that is for 2 ms, for
the new value to be accepted.
This parameter is read-only.
0b0000
0b0000...0b1111 Delayed status for digital inputs.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
Initialized
1 = Adaptive program initialized
1
Editing
1 = Adaptive program is being edited
2
Edit done
1 = Editing of adaptive program finished
3
Running
1 = Adaptive program running
4…13 Reserved
14
State changing
1 = State change in progress in adaptive
programming engine
15
Faulted
1 = Error in adaptive program
Bit
Name
Description
0
DI1
1 = Digital input 1 is ON.
1
DI2
1 = Digital input 2 is ON.
2
DI3
1 = Digital input 3 is ON.
3
DI4
1 = Digital input 4 is ON.
4
DI5
1 = Digital input 5 is ON.
5
DI6
1 = Digital input 6 is ON.
6…15 Reserved
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...