Parameters 139
Shows torque controller limitation status word.
This parameter is read-only.
0b0000
0b0000…
0b1111
Torque limitation status word.
1 = 1
Defines the drive current limit monitor time after
which action is taken as specified in the
parameter
10.00
0.00...120.00s
Current limit monitor time.
100=1
Selects how the drive reacts when the drive
reaches the current limit (
and exceeds the monitor time set by parameter
No action
None (current limit action disabled).
0
Warning
. 1
Fault
.
2
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
Undervoltage *1 = Intermediate DC circuit undervoltage
1
Overvoltage
*1 = Intermediate DC circuit overvoltage
2
Minimum
torque
*1 = Torque is being limited by
3
Maximum
torque
*1 = Torque is being limited by
4
Internal
current
1 = An inverter current limit (identified by bits 8…11) is
active
5
Load angle
(With permanent magnet motors and reluctance motors
only)
1 = Load angle limit is active, ie. the motor cannot
produce any more torque
6
Motor pullout (With asynchronous motors only)
Motor pull-out limit is active, ie. the motor cannot
produce any more torque
7
Reserved
8
Thermal
1 = Input current is being limited by the main circuit
thermal limit
9
Max current
*1 = Maximum output current (
I
MAX
) is being limited
10
User current
*1 = Output current is being limited by
11
Thermal IGBT *1 = Output current is being limited by a calculated
thermal current value
12…15 Reserved
*Only one out of bits 0…3, and one out of bits 9…11 can be on simultaneously.
The bit typically indicates the limit that is exceeded first.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...