Parameters 101
The electrical statuses of the digital inputs can
be overridden for eg. testing purposes. A bit in
parameter
is provided for
each digital input, and its value is applied
whenever the corresponding bit in this
parameter is 1.
Note: Boot and power cycle reset the force
selections (parameters
and
0b0000
0b0000...0b1111 Override selection for digital inputs.
1 = 1
Allows the data value of a forced digital input to
be changed from 0 to 1. It is only possible to
force an input that has been selected in
parameter
Bit 0 is the forced value for DI1; bit 5 is the forced
value for the DI6.
0b0000
0b0000...0b1111 Forced values of digital inputs.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Bit
Value
0
1 = Force DI1 to value of bit 0 of parameter
.
(0 = Normal mode)
1
1 = Force DI2 to value of bit 1 of parameter
(0 = Normal mode)
2
1 = Force DI3 to value of bit 2 of parameter
.
(0 = Normal mode)
3
1 = Force DI4 to value of bit 3 of parameter
(0 = Normal mode)
4
1 = Force DI5 to value of bit 4 of parameter
.
(0 = Normal mode)
5
1 = Force DI6 to value of bit 5 of parameter
.
(0 = Normal mode)
6…15 Reserved
Bit
Value
0
Force the value of this bit to D1, if so defined in parameter
1
Force the value of this bit to D3, if so defined in parameter
2
Force the value of this bit to D3, if so defined in parameter
3
Force the value of this bit to D4, if so defined in parameter
4
Force the value of this bit to D5, if so defined in parameter
5
Force the value of this bit to D6, if so defined in parameter
6…15 Reserved
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...