Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / real32
Displays the value of analog input AI2 after scaling. See
parameters
and
This parameter is read-only.
AI2 scaled value
12.22
1 = 1 / 1000 = 1
Scaled value of analog input AI2.
-32768.000 ...
32767.000
mA / uint16
Selects the unit for readings and settings related to
analog input AI2.
Note: This setting must match the corresponding
hardware setting on the drive control unit (see the
hardware manual of the drive). Control board reboot
(either by cycling the power or through parameter
) is required to validate any changes
in the hardware settings.
AI2 unit selection
12.25
2
Volts.
V
10
Milliamperes.
mA
0.100 s / real32
Defines the filter time constant for analog input AI2.
See parameter
.
AI2 filter time
12.26
1000 = 1 s / 1000 = 1
s
Filter time constant.
0.000 ... 30.000 s
0.000 mA or V /
real32
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
See also parameter
.
AI2 min
12.27
1000 = 1 mA or V /
1000 = 1 mA or V
Minimum value of AI2.
-22.000 ... 22.000 mA
or V
20.000 mA or V /
real32
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
See also parameter
.
AI2 max
12.28
1000 = 1 mA or V /
1000 = 1 mA or V
Maximum value of AI2.
-22.000 ... 22.000 mA
or V
190 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...