Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Zero / uint32
Selects the source of torque reference additive 2.
The value received from the selected source is added
to the torque reference after operating mode selection.
Because of this, the additive can be used in speed and
torque modes.
Note: For safety reasons, the additive is not applied
when an emergency stop is active.
WARNING!
If the additive exceeds the limits set by
parameters
25.11 Speed control min torque
and
25.12 Speed control max torque
, a ramp stop
may be impossible. Make sure the additive is
reduced or removed when a ramp stop is
required eg. by using parameter
.
See the control chain diagram on page
For the selections, see parameter
Torque additive 2
source
26.25
Not selected / uint32
Selects a source that forces torque reference additive
2 (see parameter
26.25 Torque additive 2 source
) to
zero.
0 = Normal operation
1 = Force torque reference additive 2 to zero.
Force torque ref add
2 zero
26.26
0
0
Not selected
1
1
Selected
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
See
Terms and abbreviations (page 130)
Other [bit]
100 ms / real32
Defines the filtering time of the torque limit.
This parameter is used to smooth the step when
changing the limit if the drive is running on torque limit.
Torque limit filter
time
26.27
1 = 1 ms / 1 = 1 ms
Torque limit filter time.
0...100 ms
300 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...