Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / uint32
Defines a start delay for the motor fan.
The delay timer starts when the control source selected
by parameter
switches on. After the delay, bit 1
of
switches on.
DOL starter on delay
35.101
1 = 1 s / 100 = 1 s
Motor fan start delay.
0...42949673 s
20 min / uint32
Defines a stop delay for the motor fan.
The delay timer starts when the control source selected
by parameter
switches off. After the delay, bit
1 of
switches off.
DOL starter off
delay
35.102
1 = 1 min / 1 = 1 min
Motor fan stop delay.
0...715828 min
Not selected; DI5
(95.20 b6) / uint32
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of
switches on),
feedback is expected within the time set by
DOL starter
feedback source
35.103
0
0
Not selected
1
1
Selected
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
See
Terms and abbreviations (page 130)
.
Other [bit]
0; 5 (95.20 b6) s /
uint32
Defines a feedback delay for the motor fan.
The delay timer starts when bit 1 of
switches
on. If no feedback is received from the fan until the
delay elapses, the action selected by
is taken.
Note: This delay is only applied at start. If the feedback
signal is lost during run, the action selected by
is taken immediately.
DOL starter
feedback delay
35.104
1 = 1 s / 1 = 1 s
Motor fan start delay.
0...42949673 s
- / uint16
Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as
the source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected
control and feedback sources, and the fault status.
This parameter is read-only.
DOL starter status
word
35.105
Status of fan control source selected by
0 = Stop requested
1 = Start requested
Start command:
b0
Parameters 353
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...