Chapter 5 Function parameter
113
Ch
ap
ter 5
E3.04 Virtual VDI5 terminal function selection
0 to 50
0
★
Virtual VDI1 ~ VDI5 on the function, are exactly as same as the DI on the control panel, can
be used as a multi-function digital quantity input, the details please refer to the F1.00 ~ F1.09 is
introduced.
E3.05
Virtual
VDI
effecti
ve
status
set
mode
Units digit
Virtual VDI1
00000
★
Invalid
0
Valid
1
Tens digit
Virtual VDI2 (0-1, same as unit digit)
Hundreds digit
Virtual VDI3 (0-1, same as unit digit)
Thousands digit
Virtual VDI4 (0-1, same as unit digit)
Ten thousands digit
Virtual VDI5 (0-1, same as unit digit)
E3.06
Virtual
VDI
status
set
Units digit
Virtual VDI1
11111
★
VD1 whether valid is decided by Virtual VDOX status
0
VD1 whether valid is decided by Virtual VDOX status
1
Tens digit
Virtual VDI2 (0-1, same as unit digit)
Hundreds digit
Virtual VDI3 (0-1, same as unit digit)
Thousands digit
Virtual VDI4 (0-1, same as unit digit)
Ten thousands digit
Virtual VDI5 (0-1, same as unit digit)
Different from ordinary digital quantity input terminals, virtual VDI state can have two
setting modes which is selected by E3.06.
When selecting VDI state is determined by the state of the corresponding virtual VDO, VDI
is valid or invalid state depending on the VDO output valid or invalid, and VDIx only binding
VDOx(x=1~5).
When choosing VDI state selection function code to set, through the binary bits of E3.05,
respectively determine the state of virtual input terminals.
Example of how to use VDI.
Example 1. Implement following function: “Inverter fault alarm and shuts down when AI1
input exceeds upper or lower frequency” .
Realize by following settings: Set VDI state decided by VDO, set VDI1 function as “ user
defined fault 1” (E3.00=44); set VDI1 terminal state effective mode decided by VDO1
(E3.06=xxx0); set VDO1 output function as “AI1 input exceeds upper & lower frequency”
(E3.11=31); so when AI1 input exceeds upper or lower frequency, VDO1 state is ON, VDI1 input
terminal state is effective, VDI1 receive user defined fault 1, inverter then alarm fault no. 27 and
shuts down.
Example 2. Implement following function: “Inverter run automatically after power-on”.
Realize by following settings: set VDI state decided by function code E3.05, set VDI1
function as “FORWARD” (E3.00=1); set VDI1 terminal state effective decided by function code
(E3.06=xxx1); set VDI1 terminal state is effective (E3.05=xxx1); set command source as “terminal
control” (F0.11=1); set protection selection as “no protection” (F7.22=0); so after inverter powered
on and initialization complete, VDI1 detected effective, and it match forward running, then
inverter starts running forwardly.
E3.07 AI1 terminal as a function selection of DI
0 to 50
0
★
E3.08 AI2 terminal as a function selection of DI
0 to 50
0
★
E3.09 reserve
E3.10
AI terminal as a
function selection of
DI
Units digit
AI1
000
★
High level effectively
0
High level effectively
1
Tens digit
AI2(same as units digit)
Hundreds digit
AI3(same as units digit)
This group function code is used when using AI as DI, when AI used as DI, and input voltage
of AI is greater than 7V, AI terminal status will be high level, when input voltage of AI is lower
than 3V, AI terminal status will be low level. For between 3V~ 7V hysteresis E3.10 is to determine