INT32U CMD
Command (answer)
INT8U
EXTIOSetupFlags Configuration flags of the external I-O
0x01 - EXTIO_SETUP_OUTPUT (EXTIO works as output if flag is set, works as input otherwise.)
0x02 - EXTIO_SETUP_INVERT (Interpret EXTIO states and fronts inverted if flag is set. Falling front as
input event and low logic level as active state.)
INT8U
EXTIOModeFlags Flags mode settings external I-O
0x0F - EXTIO_SETUP_MODE_IN_BITS (Bits of the behaviour selector when the signal on input goes to the
active state.)
0x00 - EXTIO_SETUP_MODE_IN_NOP (Do nothing.)
0x01 - EXTIO_SETUP_MODE_IN_STOP (Issue STOP command, ceasing the engine movement.)
0x02 - EXTIO_SETUP_MODE_IN_PWOF (Issue PWOF command, powering off all engine windings.)
0x03 - EXTIO_SETUP_MODE_IN_MOVR (Issue MOVR command with last used settings.)
0x04 - EXTIO_SETUP_MODE_IN_HOME (Issue HOME command.)
0x05 - EXTIO_SETUP_MODE_IN_ALARM (Set Alarm when the signal goes to the active state.)
0xF0 - EXTIO_SETUP_MODE_OUT_BITS (Bits of the output behaviour selection.)
0x00 - EXTIO_SETUP_MODE_OUT_OFF (EXTIO pin always set in inactive state.)
0x10 - EXTIO_SETUP_MODE_OUT_ON (EXTIO pin always set in active state.)
0x20 - EXTIO_SETUP_MODE_OUT_MOVING (EXTIO pin stays active during moving state.)
0x30 - EXTIO_SETUP_MODE_OUT_ALARM (EXTIO pin stays active during Alarm state.)
0x40 - EXTIO_SETUP_MODE_OUT_MOTOR_ON (EXTIO pin stays active when windings are powered.)
0x50 - EXTIO_SETUP_MODE_OUT_MOTOR_FOUND (EXTIO pin stays active when motor is connected (first
winding).)
INT8U
Reserved [10]
Reserved (10 bytes)
INT16U CRC
Checksum
Description:
Read EXTIO settings. This function reads a structure with a set of EXTIO settings from controller's memory.
Command SBRK
result_t set_brake_settings (device_t id, const brake_settings_t* brake_settings)
Command code (CMD): "sbrk" or 0x6B726273.
Request: (25 bytes)
INT32U CMD
Command
INT16U t1
Time in ms between turn on motor power and turn off brake.
INT16U t2
Time in ms between turn off brake and moving readiness. All moving commands will execute after this
interval.
INT16U t3
Time in ms between motor stop and turn on brake.
INT16U t4
Time in ms between turn on brake and turn off motor power.
INT8U
BrakeFlags
Flags.
0x01 - BRAKE_ENABLED (Brake control is enabled, if this flag is set.)
0x02 - BRAKE_ENG_PWROFF (Brake turns off power of step motor, if this flag is set.)
INT8U
Reserved
[10]
Reserved (10 bytes)
INT16U CRC
Checksum
Answer: (4 bytes)
INT32U CMD Command (answer)
Description:
Set settings of brake control.
Command GBRK
Page 229 / 345
Page 229 / 345
Summary of Contents for 8SMC5-USB
Page 30: ...Linux Page 30 345 Page 30 345 ...
Page 83: ...Connection of magnetic brake to one axis or two axis systems Page 83 345 Page 83 345 ...
Page 87: ...Scheme of buttons connection to the HDB 26 connector Page 87 345 Page 87 345 ...
Page 99: ...Page 99 345 Page 99 345 ...
Page 167: ...Vertical load capacity the maximum vertical load on the stage Page 167 345 Page 167 345 ...
Page 186: ...Click Next Click Continue anyway Page 186 345 Page 186 345 ...
Page 188: ...Page 188 345 Page 188 345 ...
Page 190: ...Page 190 345 Page 190 345 ...
Page 193: ...Page 193 345 Page 193 345 ...
Page 201: ...Select the XILab application in the Programs block Start it Page 201 345 Page 201 345 ...
Page 274: ...7 Files 1 Configuration files 2 Software Page 274 345 Page 274 345 ...
Page 331: ...Motorized Iris Diaphragms 8MID98 Motorized Iris Diaphragm Page 331 345 Page 331 345 ...
Page 338: ...8 Related products 1 Ethernet adapter Page 338 345 Page 338 345 ...
Page 339: ...8 1 Control via Ethernet 1 Overview 2 Administration Page 339 345 Page 339 345 ...