Parameter
Declaration
Data type
Address
(Inst.-DB)
Default
Value
Comment
MAN_DO
INPUT
BOOL
4.1
FALSE
This parameter is not evaluated.
SET_DO
INPUT
BOOL
4.2
FALSE
This parameter is not evaluated.
OUTP_VAL
INPUT
INT
6.0
0
Output value
JOB_REQ
INPUT
BOOL
8.0
FALSE
Job trigger (edge 0-1)
JOB_ID
INPUT
WORD
10.0
0
Job number
JOB_VAL
INPUT
DINT
12.0
0
Value for write jobs
STS_EN
OUTPUT
BOOL
16.0
FALSE
Status internal gate
STS_STRT
OUTPUT
BOOL
16.1
FALSE
This parameter is reserved.
STS_DO
OUTPUT
BOOL
16.2
FALSE
This parameter is reserved.
JOB_DONE
OUTPUT
BOOL
16.3
TRUE
Status parameter
n
0: The job has not started or is
still running.
n
1: Job has been executed. A
new job can be started.
JOB_ERR
OUTPUT
BOOL
16.4
FALSE
Status parameter
n
0: no error
n
1: Error (see
JOB_STAT
)
JOB_STAT
OUTPUT
WORD
18.0
0
The
‘output format’
for PWM and pulse train can be set via the hardware configuration.
Depending on the output format, there are the following range of values for the
output
value
:
n
Output in
‰
–
Range of values: 0 ... 1000
–
Pulse duration
= (
OUTP_VAL
/ 1000) x
period duration
n
Output format: S7 analog value
–
Pulse duration
= (
OUTP_VAL
/ 27648) x
period duration
–
Range of values: 0 ... 27648
Job number
n
00h: Job without function
n
01h: Write
period duration
for PWM and. 1 pulse train job
Range of values in dependence of the time base:
–
1ms: 1 ... 87
–
0.1ms: 1 ... 870:
–
10µs 2 ... 8700
–
1µs: 20 ... 65535
OUTP_VAL
JOB_ID
VIPA System 300S
+
Deployment I/O periphery
Pulse width modulation - PWM > SFB 49 - PULSE - Pulse width modulation
HB140 | CPU-SC | 313-5BF23 | en | 19-01