The basic format is:
ANYxx[Zyyy] / ANYxx[ ]
The ANY script will operate when xx number of devices in zone yyy go into alarm (isolated alarms do not count).
ANY3[Z20]
will operate when any 3 points in zone 20 go into alarm
ANY10[ ]
will operate when any 10 points in the panel go into alarm
Rules:
1.
The number of devices in a zone is limited to 40 therefore valid range for xx is 1 to 40.
2.
The number of zones on the panel is limited to 999 valid range for yyy is 1 to 999.
3.
If no zone number is entered, ANY will use the number of devices in alarm on the panel.
8
8
.
.
1
1
.
.
5
5
T
T
I
I
M
M
O
O
P
P
E
E
R
R
A
A
T
T
O
O
R
R
The TIM operator is intended to be used to operate a script, either by itself or in combination with other conditions,
based on dates and times of day.
The basic format is:
TIM[ <ON date and time>,<OFF date and time>,<days of week>];
Where:
Date format:
dd/mm/yy
Time format
:
hh:mm:ss
Days of the week format:
SU,MO,TU,WE,TH,FR,SA
This is processed as :"Turn ON at date1, time1, turn OFF at date2,time2, for the following days of the week"
Examples:
1.
TIM[23/01/03, 09:00:00, 23/01/03, 17:00:00];
This script will turn on at 9 am and turn off at 5 pm on the 23rd of Jan 2003.
2.
TIM[09:00:00, 17:00:00];
This script will turn on at 9 am and turn off at 5 pm every day
3.
TIM[17:00:00, 09:00:00];
This script will turn on at 5pm and turn off at 9am the next day, every day
4.
TIM[00:00:00, 09:00:00, MO,WE,FR];
This script will turn on at midnight( 00:00:00) and turn off at 9 am, every Monday, Wednesday and Friday
5.
TIM[SA,SU];
This script will turn on at midnight Saturday Morning and turn off at midnight Sunday evening.
6.
TIM[MO5];
This script will turn on at midnight Monday morning and stay on for 5 days (Friday midnight).
Rules:
1.
There must be at least a date/time, or a day entry.
2.
If there is an ON date, there must be an OFF date.
3.
If there is an ON time, there must be an OFF time.
4.
If ALL seven days are entered or if no days are entered, the script will operate every day.
5.
The order of days is not significant.
6.
If a date range, does not include a day specified, the script will not operate
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......