95
VCCX2 Controller Technical Guide
TREND LOG ENUMERATED VALUES
Item Description
Value
Description
Mode
0
Unoccupied
1
Occupied
2
Push Button Override Active
HVAC
0
Off
1
Vent Mode
2
Cooling Mode
3
Heating Mode
4
Vent Dehumidify Mode
5
Cool Dehumidify Mode
6
Heat Dehumidify Mode
7
Warm-up Mode
8
Fan Purge Mode
9
Defrost Mode
10
Pushbutton Override Active
RSMZ TREND LOG BIT STRINGS - COMPSTAT
Item
Bit Value
Description
1Comp1Stat
2Comp1Stat
3Comp1Stat
3Comp2Stat
4Comp1Stat
5Comp1Stat
6Comp1STat
6Comp2Stat
0
1
Configured
1
2
Enabled
2
4
Running
3
8
Failed
4
16
Lockout
5
32
MinRunFlag
6
64
MinRunPending
7
128
MinOffFlag
8
256
MinOffPending
9
512
StageUpConditionsMet
10
1024
StageDwnConditionsMet
11
2048
StageUpFlag
12
4096
StageDwnFlag
13
8192
CoilTempSatisfied
RSMZ TREND LOG BIT STRINGS - RSM ALARMS
Item
Bit Value
Description
1RSMAlrms
2RSMAlrms
3RSMAlrms
4RSMAlrms
5RSMAlrms
6RSMAlrms
0
1
LowSuction
1
2
UnsafeSuction
2
4
TripHighDiscPSI_Comp1
3
8
Compressor1_NotRunning
4
16
Compressor2_NotRunning
5
32
LowSuperheat
6
64
HighDischargeTemperature
7
128
DMQ_NoDetect
8
256
ModBusSlaveCommTO
9
512
LowSuctionComp2Off
10
1024
TripHighDiscPSI_Comp2
11
2048
HighSuperheat
12
4096
HighEvapTemp
SEQUENCE OF OPERATIONS
RSMZ Trend Logs and Trend Log Enumerated Values
Table 8: Trend Log Enumerated Values
Table 9: RSMZ Module Comp Status Trend Log
Table 10: RSMZ Module RSM Alarm Trend Log