Logical Command and Speed Reference
7-14 | CFW500
7
Table 7.5:
Status word
Bit
Function
Description
0 to 3
Reserved.
4
Fs Reduction.
0:
Output frequency reduction inactive.
1:
Output frequency reduction active.
5
Sleep Mode.
0:
Sleep mode inactive.
1:
Sleep mode active.
6
Deceleration Ramp.
0:
No deceleration.
1:
Inverter decelerating.
7
Acceleration Ramp.
0:
No acceleration.
1:
Inverter accelerating.
8
Frozen Ramp.
0:
Ramp operating in normal conditions.
1:
The path of the ramp is frozen by some command source or internal function.
9
Setpoint Ok.
0:
Output frequency has not reached reference yet.
1:
Output frequency reached reference.
10
DC Link Regulation.
0:
DC Link Regulation or Current Limitation inactive.
1:
DC Link Regulation or Current Limitation active (P0150).
11
Configuration in
50 Hz.
0:
Factory default loaded in 60 Hz (P0204 = 5).
1:
Factory default loaded in 50 Hz (P0204 = 6).
12
Ride-Through.
0:
No execution of Ride-Through.
1:
Executing Ride-Through.
13
Flying Start.
0:
No execution of Flying Start.
1:
Executing Flying Start.
14
DC Braking.
0:
DC breaking inactive.
1:
DC breaking active.
15
PWM Pulses.
0:
PWM voltage pulses in the output disabled.
1:
PWM voltage pulses in the output enabled.
P0682 – Serial Control
P0684 – CANopen/DeviceNet/Profibus DP/Ethernet Control
Adjustable
Range:
0000h to FFFFh
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ, NET
Description:
The inverter control word for a certain source is accessible for reading and writing, but read only access is
permitted for the other sources. The inverter has a common word for interface, which is defined by the function
of its bits separately as per
.
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...