CET Electric Technology
96
Object 12 - Control Relay Outputs
Responds to Function Codes: 03 (Select), 04 (Operate) and 05 (Direct Operate), Variation 1, Qualifier
0x28, with a Count of 1 only. Only one control object at a time may be specified.
Point
Description
Format
Range
0
Reserved
UINT8
1
Clear All Energy Registers
UINT8
N/A
2
Reserved
UINT8
N/A
3
Clear Peak Demand of This Month (Since Last Reset)
UINT8
N/A
4
Clear All Demand Registers
UINT8
N/A
5
Clear Max/Min Logs of This Month (Since Last Reset)
UINT8
N/A
6
Clear All Max./Min. Log
UINT8
N/A
7
Clear Device Operating Time
UINT8
N/A
8
Clear All Data
UINT8
N/A
9
Clear DI1 Pulse Counter
UINT8
N/A
10
Clear DI2 Pulse Counter
UINT8
N/A
11
Clear DI3 Pulse Counter
UINT8
N/A
12
Clear DI4 Pulse Counter
UINT8
N/A
13
Reserved
UINT8
14
Reserved
UINT8
15
Clear All Pulse Counters
UINT8
N/A
16
DO1
UINT8
Bit Flags
17
DO2
UINT8
Bit Flags
Please refer to the
DNP V3.00 Data Object Library
document for a detailed description of the Object
Coding format for the Control Relay Output Block as well as the meanings of the returned Status.
Object 20 - 32-BIT Binary Counters - Primary Readings (Included in Class 0 responses)
Read with Object 20, Variation 5, and Qualifier 6.
Point
Description
Format
Unit
Scale
Range
0
kWh Import
INT32
kWh
10
0-999,999,999
1
kWh Export
INT32
kWh
2
kWh Net
INT32
kWh
3
kWh Total
INT32
kWh
4
kvarh Import
INT32
kvarh
5
kvarh Export
INT32
kvarh
6
kvarh Net
INT32
kvarh
7
kvarh Total
INT32
kvarh
8
kVAh
INT32
kVAh
9
kvarh Q1
INT32
kvarh
10
kvarh Q2
INT32
kvarh
11
kvarh Q3
INT32
kvarh
12
kvarh Q4
INT32
kvarh
13
Interval kWh Import
INT32
kWh
14
Interval kWh Export
INT32
kWh
15
Interval kvarh Import
INT32
kvarh
16
Interval kvarh Export
INT32
kvarh
17
Interval kVAh
INT32
kVAh
18
DI1 Pulse Counter
UINT32
1
1
0-999,999,999
19
DI2 Pulse Counter
UINT32
1
20
DI3 Pulse Counter
UINT32
1
21
DI4 Pulse Counter
UINT32
1
Object 20 - 16-BIT Binary Counters - Primary Readings (Included in Class 0 responses)
Read with Object 20, Variation 6, and Qualifier 6.
Point
Description
Format
Range
0
Energy Scale
UINT16
10
1
I0-I4,Ir, PF, Scale
UINT16
1000
2
Scale for U, Freq, Phase Angle, THD, TDD, K Factor, Crest Factor
and Unbalance
UINT16
100
3
Scale for AI and Power
UINT16
1
4
Firmware Version
1
UINT16
0-65535
Notes: