CET Electric Technology
83
9604
WO
Clear All Demand Registers
5
9605
WO
Clear Max/Min Logs of This Month
(Since Last Reset)
6
9606
WO
Clear All Max/Min Log
7
9607
WO
Clear Device Operating Time
9608
WO
Clear All Data
8
9609
WO
Clear SOE Log
9610
WO
Clear DI1 Pulse Counter
9611
WO
Clear DI2 Pulse Counter
9612
WO
Clear DI3 Pulse Counter
9613
WO
Clear DI4 Pulse Counter
9614
WO
Clear Daily Freeze Log
9615
WO
Clear Monthly Freeze Log
9616
WO
Reserved
9617
WO
Send Testing Email
9618
WO
Clear All Pulse Counters
9619
WO
Clear Data Recorder #1 Log
9620
WO
Clear Data Recorder #2 Log
9621
WO
Clear Data Recorder #3 Log
9622
WO
Clear Data Recorder #4 Log
9623
WO
Clear Data Recorder #5 Log
9624
WO
Clear All Data Recorder Log
Table 5-54 Clear Control
Notes:
1)
Writing 0xFF00 to the Clear Historical Monthly Energy Log register means to clear the Monthly Energy Log of the last 1 to
12 months, excluding the Monthly Energy Log for the Present Month.
2)
Writing 0xFF00 to the Clear All Energy Registers register to clear 3-Phase Total Energy registers and Phase A/B/C Energy
registers, including TOU Energy and Interval Energy.
3)
Writing 0xFF00 to the Clear Present Monthly Energy Log register means to clear the Monthly Energy Log of the Present
Month.
4)
Writing 0xFF00 to the Clear Peak Demand of This Month register to clear Peak Demand Log of This Month (Since Last Reset)
when the Self-Read Time register is set for automatic Self-Read operation. The Peak Demand of Last Month will not be
cleared. If the Self-Read Time register is set for manual operation with a register value of 0xFFFF, the Peak Demand of This
Month (Since Last Reset) will be transferred to the Peak Demand of Last Month (Before Last Reset) and then cleared.
5)
Writing 0xFF00 to the Clear All Demand register to clear all Demand registers and logs, including Real-time Present Demand,
Peak Demand Log of This Month (Since Last Reset) and Last Month (Before Last Reset).
6)
Writing 0xFF00 to the Clear Max/Min Log of This Month register to clear the Max/Min log of This Month (Since Last Reset)
when the Self-Read Time register is set for automatic Self-Read operation. The Max/Min log of Last Month will not be
cleared. If the Self-Read Time register is set for manual operation with a register value of 0xFFFF, the Max/Min log of This
Month (Since Last Reset) will be transferred to the Max/Min log of Last Month (Before Last Reset) and then cleared.
7)
Writing 0xFF00 to the Clear All Max/Min Log register to clear both the Max/Min Log of This Month (Since Last Reset) and
the Max/Min Log of Last Month (Before Last Reset).
8)
Writing 0xFF00 to the Clear All Data register to perform the Clear operation for the actions specified in registers # 9600 to
# 9607, registers # 9609 to # 9615, registers # 9618 to 9624 and Interval Energy Measurements.
5.16 Meter Information
Register
Property
Description
Format
Note
60200~60219 9800~9819
RO
Meter model
1
UINT16
See Note 1)
60220
9820
RO
Firmware Version
UINT16
e.g. 10000 shows the
version is V1.00.00
60221
9821
RO
Protocol Version
UINT16
e.g. 10 shows the
version is V1.0
60222
9822
RO
Firmware Update
Date: Year-2000
UINT16
e.g. 140110 means
January 10, 2014
60223
9823
RO
Firmware Update
Date: Month
UINT16
60224
9824
RO
Firmware Update
Date: Day
UINT16
60225
9825
RO
Serial Number
UINT32
e.g. 1701030100 means
the 100
th
PEM353 that
was manufactured on
January 3
rd
, 2017
60227
9827
RO
Reserved
UINT16
60228
9828
RO
Reserved
UINT16
60229
9829
RO
Extension Module
UINT16
See Note 2)
Table 5-55 Meter Information
Notes: