CET Electric Technology
98
60
U2 (-ve Sequence Voltage)
2
INT32
61
U0 (Zero Sequence Voltage)
2
INT32
62
I1 (+ve Sequence Current)
2
INT32
x1000
A
63
I2 (-ve Sequence Current)
2
INT32
64
I0 (Zero Sequence Current)
2
INT32
65
Ia TDD
INT32
x100
-
66
Ib TDD
INT32
67
Ic TDD
INT32
68
Ia K Factor
INT32
69
Ib K Factor
INT32
70
Ic K Factor
INT32
71
Ia Crest Factor
INT32
72
Ib Crest Factor
INT32
73
Ic Crest Factor
INT32
74
Voltage Unbalance
INT32
75
Current Unbalance
INT32
76
Uan/Uab THD
INT32
77
Ubn/Ubc THD
INT32
78
Ucn/Uca THD
INT32
79
Ia THD
INT32
80
Ib THD
INT32
81
Ic THD
INT32
82
Ia Present Demand
INT32
x1000
A
83
Ib Present Demand
INT32
84
Ic Present Demand
INT32
85
∑kW Present Demand
INT32
x1
W
86
∑kvar Present Demand
INT32
var
87
∑kVA Present Demand
INT32
VA
88
Ia Peak Demand of This Month (Since Last Reset)
INT32
x1000
A
89
Ib Peak Demand of This Month (Since Last Reset)
INT32
90
Ic Peak Demand of This Month (Since Last Reset)
INT32
91
∑kW Peak Demand of This Month (Since Last Reset)
INT32
x1
W
92
∑kvar Peak Demand of This Month (Since Last Reset)
INT32
var
93
∑kVA Peak Demand of This Month (Since Last Reset)
INT32
VA
94
Ia Peak Demand of Last Month (Before Last Reset)
INT32
x1000
A
95
Ib Peak Demand of Last Month (Before Last Reset)
INT32
96
Ic Peak Demand of Last Month (Before Last Reset)
INT32
97
∑kW Peak Demand of Last Month (Before Last Reset)
INT32
x1
W
98
∑kvar Peak Demand of Last Month (Before Last Reset)
INT32
var
99
∑kVA Peak Demand of Last Month (Before Last Reset)
INT32
VA
Notes:
1)
When the Wiring Mode is 1P2W L-N or 1P2W L-L, the L2 and L3 phase voltages and currents have no meaning, and their
registers are reserved.
2)
When the Wiring Mode is 1P2W L-N, 1P2W L-L or 1P3W, the Sequence Components U1/I1, U2/I2 and U0/I0 have no
meaning and their registers are reserved.
Object 40 - Analog Output Status Objects
Read with Object 40, Variation 2, and Qualifier 6.
Point
Property
Description
Format
Range
0
RO
Class 0 Objects Set
UINT16
0-65535
Object 41 - Analog Output Command Objects
Responds to Function Codes: 03 (Select), 04 (Operate) and 05 (Direct Operate), Variation 2, Qualifier
0x28, with a Count of 1 only.
Point
Property
Description
Format
Range
0
WO
Class 0 Objects Set
UINT16
0-65535
Note: The following table illustrates the details of Bit Values for Class 0 Points.
Bit Point
Descriptions
Value
Bit 0
Object 1 - Binary Input Status Included in Class 0 responses?
0=No, 1=Yes (default)
Bit 1
Object 10 - Binary Output States Included in Class 0 responses?
0=No, 1=Yes (default)
Bit 2
Object 20 - 32 BIT Binary Counters Included in Class 0 responses?
0=No, 1=Yes (default)
Bit 3
Object 20 - 16 BIT Binary Counters Included in Class 0 responses?
0=No, 1=Yes (default)
Bit 4
Object 30 -Analog Inputs Included in Class 0 responses?
0=No, 1=Yes (default)