CET Electric Technology
73
6037
RW
Backlight Time-out
UINT16
0 to 60 (mins), 5*
6038
RW
System Language
UINT16
1=English
6039
RW
Date Format
UINT16
0=YYMMDD*
1=MMDDYY
2=DDMMYY
6040
RW
Delimiter
5
UINT16
0=Option 1*, 1=Option 2
See Note 4
6041
RW
Monthly Freeze
Self-Read Time
6
UINT16
0*
6042
RW
Daily Freeze
Self-Read Time
7
UINT16
0*
6043
RW
1
st
parameter of the Default
Display
8
UINT16
0 to 36, 7*
6044
RW
2
nd
parameter of the Default
Display
8
UINT16
0 to 36, 11*
6045
RW
3
rd
parameter of the Default
Display
8
UINT16
0 to 36, 12*
6046
RW
4
th
parameter of the Default
Display
8
UINT16
0 to 36, 15*
6047
RW
EN Period
9
UINT16
5 to 60* min
6048
RW
Setpoint Splash LCD Alarm
UINT16
0= Enabled*, 1= Disabled
6049
RW
Current Threshold of Device
Operating Time
UINT16
1* to 1000 (x0.001In)
6050
RW
kvarh Calculation
UINT16
0= RMS*, 1= kvarh Fund.
6051
RW
DNP Polling Object
10
UINT16
0 to 65535, 0x3F*
6052
RW
SNTP Enable
UINT16
0=Disabled*, 1=Enabled
6053
RW
Time Zone
11
UINT16
0 to 32, 26*
6054
RW
SNTP Sync. Interval
12
UINT16
1 to 1440 (min), 60*
6055
RW
SNTP Server Address
UINT32
If IP address is
192.168.8.94, write
“0xC0A8085E” to this
register
6057
RW
SMTP IP Port
UINT16
0 to 65535, 25*
6058
RW
SMTP Server Address
UINT32
If address is 191.0.0.6,
write “0XBF000006” to this
register
6060~6095
RW
Sender Email
UINT16
See Note (13)
6096~6115
RW
Logon Password
UINT16
See Note (14)
6116~6151
RW
Receiver Email
UINT16
See Note (15)
Table 5-33 Basic Setup Parameters
Notes:
1)
The value of [PT Primary/PT Secondary] cannot exceed 10000.
2)
There are two ways to calculate THD:
THDf:
THD
f
=
√∑
I
n
2
∞
n=2
I
1
×100%
where I
1
represents the RMS value of the fundamental component, and I
n
represents the RMS value for the n
th
harmonic
with n for harmonic order.
THDr:
THDr
=
√∑
I
n
2
∞
n=2
√∑
I
n
2
∞
n=1
×100%
where I
n
represents the RMS value for the n
th
harmonic with n for harmonic order.
3)
The Self-Read Time applies to both the Peak Demand Log as well as the Max/Min Log and supports the following three
options:
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read
Time = (Day x 100 + Hour) where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-
Read will take place at 12:00pm on the 15th day of each month.
A 0xFFFF value means the automatic self-read operation is disabled and the log will be transferred manually.
4)
The Self-Read Time applies to the Monthly Energy Log supports the following two options:
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read
Time = (Day x 100 + Hour) where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-
Read will take place at 12:00pm on the 15th day of each month.
5)
The Delimiter setup register supports two options, 1 and 2: