5.12.4 Alternate Days
Each Alternate Day is assigned a Daily Profile and has a higher priority than Season. If a particular date
is set as an Alternate Day, its assigned Daily Profile will override the “normal” Daily Profile for this day
according the TOU settings.
The PMC-53A-E has two sets of Alternate
Days setup parameters, one for each TOU. The Base Addresses
for the two sets are 7700 and 8700, respectively, where the Register Address = Base A Offset.
For example, the register address for TOU #2’s Alternative Day #2’s Date is 8700+3 = 8703.
Offset
Property
Description
Format
Range/Default*
0
RW
Alternate Day #1 Date¹
UINT32
Table 5-51
2
RW
Alternate Day #1 Daily Profile
UINT16
0* to 19
3
RW
Alternate Day #2 Date¹
UINT32
Table 5-51
5
RW
Alternate Day #2 Daily Profile
UINT16
0* to 19
6
RW
Alternate Day #3 Date¹
UINT32
Table 5-51
8
RW
Alternate Day #3 Daily Profile
UINT16
0* to 19
9
RW
Alternate Day #4 Date¹
UINT32
Table 5-51
11
RW
Alternate Day #4 Daily Profile
UINT16
0* to 19
12
RW
Alternate Day #5 Date¹
UINT32
Table 5-51
14
RW
Alternate Day #5 Daily Profile
UINT16
0* to 19
15
RW
Alternate Day #6 Date¹
UINT32
Table 5-51
17
RW
Alternate Day #6 Daily Profile
UINT16
0* to 19
18
RW
Alternate Day #7 Date¹
UINT32
Table 5-51
19
RW
Alternate Day #7 Daily Profile
UINT16
0* to 19
21
RW
Alternate Day #8 Date¹
UINT32
Table 5-51
22
RW
Alternate Day #8 Daily Profile
UINT16
0* to 19
24
RW
Alternate Day #9 Date¹
UINT32
Table 5-51
25
RW
Alternate Day #9 Daily Profile
UINT16
0* to 19
27
RW
Alternate Day #10 Date¹
UINT32
Table 5-51
29
RW
Alternate Day #10 Daily Profile
UINT16
0* to 19
…
…
Table 5-51
…
…
0* to 19
240
RW
Alternate Day #81 Date¹
UINT32
Table 5-51
162
RW
Alternate Day #81 Daily Profile
UINT16
0* to 19
243
RW
Alternate Day #82 Date¹
UINT32
Table 5-51
245
RW
Alternate Day #82 Daily Profile
UINT16
0* to 19
246
RW
Alternate Day #83 Date¹
UINT32
Table 5-51
248
RW
Alternate Day #83 Daily Profile
UINT16
0* to 19
249
RW
Alternate Day #84 Date¹
UINT32
Table 5-51
251
RW
Alternate Day #84 Daily Profile
UINT16
0* to 19
252
RW
Alternate Day #85 Date¹
UINT32
Table 5-51
254
RW
Alternate Day #85 Daily Profile
UINT16
0* to 19
255
RW
Alternate Day #86 Date¹
UINT32
Table 5-51
256
RW
Alternate Day #86 Daily Profile
UINT16
0* to 19
258
RW
Alternate Day #87 Date¹
UINT32
Table 5-51
260
RW
Alternate Day #87 Daily Profile
UINT16
0* to 19
261
RW
Alternate Day #88 Date¹
UINT32
Table 5-51
263
RW
Alternate Day #88 Daily Profile
UINT16
0* to 19
264
RW
Alternate Day #89 Date¹
UINT32
Table 5-51
266
RW
Alternate Day #89 Daily Profile
UINT16
0* to 19
267
RW
Alternate Day #90 Date¹
UINT32
Table 5-51
269
RW
Alternate Day #90 Daily Profile
UINT16
0* to 19
Table 5-50 Alternate Days Setup
Note:
1)
The following table illustrates the data structure of the Date register:
Byte 3
Byte 2
Byte 1
Byte 0
Reserved
Year-2000 (0-37)
Month (1-12)
Day (1-31)
Table 5-51 Date Format
When the Year and/or Month are set as 0xFF, it means the Alternate Day is repetitive by year and/or month, i.e. the same day of
every year or every month is an Alternate Day.
5.13 Time