NEW
n
0100
16
- 0103
16
Initializes scan list n to null. Any previous scan items assigned to this list
are lost.
NEWL
0104
16
Initializes “ List-of-Lists” to null. Any previous Scan Lists assigned to this
list are lost.
SCPCHAR <
scp_number
> <
attributes
>
0830
16
Sends an SCP attributes word to the Control Processor describing the
characteristics of the SCP at installed at
<
scp_number
>
. The format of the
attributes word is as follows:
15
14 - 6
5
4
3
2
1
0
SCP
Present
Not
Assigned
Gain is 1
±
2ppm
SCP can
output
signals
SCP can
sense
voltage
SCP has
programmable
current
SCP has
programmable
cutoff frequency
SCP has
programmable
gain
SCPGAINS
0820
16
Causes the Control Processor to access SCP registers to determine the
channel gain settings for each
ASSIGN
ed channel. The channel gain
settings are used to relate A/D output to input voltage for EU conversions
and voltage readings. Execute
SCPGAINS
command after establishing
channel to EU conversion linkage with the
ASSIGN
command.
CVT Commands
CVTINIT
0420
16
This command causes the entire Current Value Table to be loaded with
IEEE-754 Not-A-Number (7FFF FFFF hex).
372 Register-Based Programming
Appendix D
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com