FC6A S
ERIES
MICROS
MART
L
ADDER
P
ROGRAMMING
M
ANUAL
FC9Y-B1726
16-1
16: C
OORDINATE
C
ONVERSION
I
NSTRUCTIONS
Introduction
XYFS (XY Format Set)
Valid Devices
For valid device address ranges, see "Device Addresses" on page 2-1.
When T (timer) or C (counter) is used as X0 through Xn or Y0 through Yn, the timer/counter current value (TC or CC) is displayed.
S1 (Format number)
Select a format number 0 through 7. A maximum of 8 formats for XY conversion can be set.
Xn (X value), Yn (Y value)
Enter values for the X and Y coordinates. Two different data ranges are available depending on the data type.
Valid Data Types
This chapter describes the coordinate conversion
instructions that convert one data point to another
value using the linear relationship between the values
of X and Y.
(X0, Y0)
(X1, Y1)
(X2, Y2)
X
Y
When input is on, the format for XY conversion is set. The XY
coordinates define the linear relationship between X and Y.
No. of XY Coordinates
n
2 to 32
0
≤
n
≤
31
XYFS(*)
S1
*
Y0
*****
Xn
*****
.....
X0
*****
Yn
*****
Device
Function
I
Q
M
R
T
C
D
P
Constant
Repeat
S1 (Source 1)
Format number
—
—
—
—
—
—
—
—
0 to 7
—
X0 through Xn
X value
X
X
X
X
X
X
X
—
0 to 65,535
—
Y0 through Yn
Y value
X
X
X
X
X
X
X
—
0 to 65,535
–32,768 to 32,767
—
Data Type
Word
Integer
Xn (X value)
0 to 65,535
0 to 65,535
Yn (Y value)
0 to 65,535
–32,768 to 32,767
Valid Coordinates
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is assigned as Xn or Yn, 16
points are used.
When a word device such as T (timer), C (counter), or D (data register) is assigned as Xn or Yn, 1 point is used.
I (integer)
X
D (double word)
—
L (long)
—
F (float)
—
Y
0
65,535
65,535
X
Y
0
32,767
–32,768
X
65,535
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1726 7 FC6A SERIES Ladder Programming Manual ...
Page 8: ...Preface 7 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 32: ...1 OPERATION BASICS 1 20 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 96: ...3 INSTRUCTIONS REFERENCE 3 18 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 130: ...4 BASIC INSTRUCTIONS 4 34 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 192: ...9 SHIFT ROTATE INSTRUCTIONS 9 12 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 272: ...12 DISPLAY INSTRUCTIONS 12 24 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 284: ...14 REFRESH INSTRUCTIONS 14 6 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 502: ...25 DATA LOG INSTRUCTIONS 25 22 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 546: ...26 SCRIPT 26 44 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 598: ...APPENDIX A 14 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...