Legrand PDU User Guide 299
Setting the Maximum Number of Active Powered Dry Contact Actuators
This command determines the upper limit of "active" powered dry contact actuators on one Legrand PDU
device.
config:#
pdu activePoweredDryContactLimit <number>
Variables:
<number> is the number representing the maximum number of active powered dry contact actuators. Its
value ranges between 0 to 24.
Note: An "active" actuator is the one that is turned ON.
Examples
This section illustrates several PDU configuration examples.
Example 1 - PDU Naming
The following command assigns the name "my px12" to the PDU.
config:#
pdu name "my px12"
Example 2 - Outlet Sequence
The following command causes a 10-outlet PDU to first power on the 8th to 6th outlets and then the rest of
outlets in the ascending order after the PDU powers up.
config:#
pdu outletSequence 8-6,1-5,9,10
Example 3 - Outlet Sequence Delay
The following command determines that the outlet 1's delay is 2.5 seconds, outlet 2's delay is 3 seconds,
and the delay for outlets 3 through 5 is 10 seconds.
config:#
pdu outletSequenceDelay 1:2.5;2:3;3-5:10
Example 4 - Non-Critical Outlets
The following command sets outlets 1, 2, 3, 7, and 9 to be critical outlets, and 4, 5, 6, 8, 10, 11 and 12 to be
non-critical outlets on a 12-outlet Legrand PDU.
config:#
pdu nonCriticalOutlets 1-3,7,9:false;4-6,8,10-12:true
Network Configuration Commands
A network configuration command begins with
network
. A number of network settings can be changed
through the CLI, such as the IP address, transmission speed, duplex mode, and so on.
Configuring IPv4 Parameters
An IPv4 configuration command begins with
network ipv4
.