Diagnostics and Troubleshooting
PLX82-EIP-PNC ♦ Communication Gateway
User Manual
EtherNet/IP™ Server to PROFINET Controller
Page 142 of 154
ProSoft Technology, Inc.
July 24, 2018
9.3.11 PNC Status Data in Upper Memory
The PNC driver has an associated status data area located in the PLX82-EIP-
PNC
’s upper memory. The
Data Map
functionality can be used to map this data
into the normal user data range of the PLX82-EIP-PNC
’s database. All the status
values are initialized to zero (0) at power-up, cold boot and during warm boot.
PNC Status
Address Range
Description
Number of Input Messages
13000
Total number of write messages to PLC
Internal DPM Input Status Count 13001
Total number of write error messages
Internal DPM Input Status
13002
Error write message status (See tables below)
Number of Output Messages
13004
Total number of read messages from PLC
Internal DPM Output Status
Count
13005
Total number of read error messages
Internal DPM Output Status
13006
Error read message status (See tables below)
Connection Count
13008
Total number of Connections
Communication Status
13009
Connection Status: 0 (Disconnected) or 1
(Connected)
Device Status (36)
13010
36 PN Device Status:
0 or an error number (See tables below)
Input IOPS Information
13082
Input State information (See tables below)
Output IOPS Information
13348 (Not In Use) Output State information
Internal DPM Input and Output Status Codes
Status Code Description
0x00000000
No error
0x800B0001
Driver was not correctly initialized during startup or driver is already closed
0x800B0002
Initialization state error. Hardware does not show correct or expected states and
information after a reset or bootupt
0x800B0003
Driver read state error
0x800B0004
The function is in use by another program instance or application
0x800B0005
General error during download (e.g. bootloader could not be downloaded or started)
0x800B0006
Wrong driver version
0x800B0030
The driver is not loaded/running. Failed to open or start the driver.
0x800B0031
Failed to initialize the driver
0x800B0032
Channel not initialized
0x800B0033
Function call into the driver failed
0x800B0034
Driver was not opened by calling Driver Open function
0x800C0010
Dual port memory not accessible (e.g. board not found, wrong dual port memory content)
0x800C0011
The device is not ready. The system device or communication channel is not working
0x800C0012
The device is not running. The communication channel is not configured
0x800C0013
Watchdog test failed
0x800C0015
Error in handshake flags
0x800C0016
Send mailbox is full
0x800C0017
Send packet timeout
0x800C0018
Receive packet timeout
0x800C0019
No packet available