PLX82-EIP-PNC ♦ Communication Gateway
Configuring the EtherNet/IP Driver
EtherNet/IP™ Server to PROFINET Controller
User Manual
ProSoft Technology, Inc.
Page 47 of 154
July 24, 2018
Class 3 Client/UClient [x] Commands Controller Tag Access
Parameter
Value
Description
Enable
Enable
Disable
Conditional Write
Specifies if the command should be executed and under what conditions.
E
NABLE
- The Command is executed each scan of the command list
D
ISABLE
- The command is disabled and will not be executed
C
ONDITIONAL
W
RITE
- The Command executes only if the internal data
associated with the command changes
Internal Address
0 to 9999
Specifies the database address in the modules internal database to be
associated with the command. If the command is a read function, the data
received in the response message is placed at the specified location. If the
command is a write function data used in the command is sourced from
the specified location.
Poll Interval
0 to 65535
Specifies the minimum interval to execute continuous commands. The
parameter is entered in 1/10 of a second. If a value of 100 is entered for a
command the command executes no more frequently than every 10
seconds.
Reg Count
1 to 125
Specifies the number of data points to be read from or written to the target
device.
Swap Code
None
Word swap
Word and Byte swap
Byte swap
Specifies if the data from the server is to be ordered differently than it was
received. This parameter is typically used when dealing with floating-point
or other multi-register values.
N
ONE
- No change is made (abcd)
W
ORD SWAP
- The words are swapped (cdab)
W
ORD AND
B
YTE SWAP
- The words and bytes are swapped (dcba)
B
YTE SWAP
- The bytes are swapped (badc)
IP Address
xxx.xxx.xxx.xxx
Specifies the IP address of the target device to be addressed by this
command
Slot
-1
Specifies the slot number for the device. Use a value of -1 when
interfacing to a PLC5 These devices do not have a slot parameter. When
addressing a processor in a ControlLogix or CompactLogix, the slot
number corresponds to the slot in the rack containing the controller being
addressed.
Func Code
332
333
Specifies the function code to be used in the command.
332 - CIP Data Table Read
333 - CIP Data Table Write
Data Type
Bool
SINT
INT
DINT
REAL
DWORD
Specifies the data type of the target controller tag name.
Tag Name
Specifies the controller tag in the target PLC.
Offset
0 to 9999
Specifies the offset database where the value corresponds to the Tag
Name parameter.
Comment
Optional 32 character comment for the command.
Summary of Contents for PLX82-EIP-PNC
Page 4: ......