Diagnostics and Troubleshooting
PLX82-EIP-PNC ♦ Communication Gateway
User Manual
EtherNet/IP™ Server to PROFINET Controller
Page 104 of 154
ProSoft Technology, Inc.
July 24, 2018
9.2.5 Acyclic Read/Write PNIO Remote Procedure Call Status
Status Code
Description
0x00000000
Status OK
0xC02E0010
Initiating CLRPC - Client failed
0xC02E0011
Initiating CLRPC - Server failed
0xC02E0012
Initiating CLRPC - Endpoint Mapper failed
0xC02E0013
Creating message queue failed
0xC02E0014
Identifying Irv_EDD failed
0xC02E0015
Getting the MAC address failed
0xC02E0100
Generic RPC-error code. See Acyclic Read/Write Communication Status for details
0xC02E0101
There was not enough memory allocated to receive the entire I/O device's Connect
Response PDU. Most likely, it contains a very large ModuleDiff-Block
0xC02E0102
The fatal error callback function is already registered
0xC02E0200
Error while sending an internal message to another task
0xC02E0201
Creating a TLR-Timer-packet in RPC task failed due to insufficient memory
0xC02E0202
The reference counter value is invalid
0xC02E0203
The port handle is invalid
0xC02E0204
The soft timer is already active (expected inactive)
0xC02E0300
The parameter "uiMaxReg" (maximum amount of RPC mapper registrations) is invalid
0xC02E0301
The requested endpoint mapper index is invalid
0xC02E0303
The state of endpoint mapper is invalid for this request
0xC02E0304
The endpoint mapper is waiting for close confirmation and therefore it's status is invalid
for this request
0xC02E0305
The status of endpoint mapper is unknown
0xC02E0306
The status of endpoint mapper is not "Ready"
0xC02E0307
Invalid parameter
0xC02E0308
CLRPC_EPMap_Deregister_req() is not allowed because at least one RPC server is
registered to this endpoint mapper
0xC02E0400
An error occurred during server initialization
0xC02E0401
The maximum number of registered RPC-Servers is exceeded or the maximum number
of outstanding requests is exceeded
0xC02E0402
Creating TLR timer for RPC server failed
0xC02E0403
There is no RPC server registered that could be de-registered
0xC02E0405
The handle to endpoint mapper is invalid
0xC02E0406
The status of endpoint mapper is invalid
0xC02E0407
The handle to RPC server instance is invalid
0xC02E0408
There is at least one object register to the RPC server instance;
CLRPC_ServerDeregister_req() cannot proceed
0xC02E0409
Invalid parameter "ulMaxRecv" in request packet
0xC02E040A
Invalid parameter "ulMaxSend" is request packet
0xC02E040B
Invalid RPC server element "ptElem". Internal RPC error
Summary of Contents for PLX82-EIP-PNC
Page 4: ......