7-58
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
F81
16 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 1 GROUND CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For 2 A < CT PRIMARY
≤
200 A
Format: Unsigned value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Unsigned value
Example: 1234 stored as 1234
For CT PRIMARY greater than 2000 A
Format: Unsigned value, scaled by 10
Example: 12340 stored as 1234
F82
16 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 2 GROUND CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234)
For 2 A < CT PRIMARY
≤
20 A
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For 200 A < CT PRIMARY
≤
200 A
Format: Unsigned value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Unsigned value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Unsigned value, scaled by 10
Example: 12340 stored as 1234
F83
16 bits
UNSIGNED VALUE
AUTORANGING BASED ON
WINDING 3 GROUND CT PRIMARY
For CT PRIMARY
≤
2 A
Format: Unsigned value, 3 decimal places
Example: 1.234 stored as 1234
For 2 A < CT PRIMARY
≤
20 A
Format: Unsigned value, 2 decimal places
Example: 12.34 stored as 1234
For 20 A < CT PRIMARY
≤
200 A
Format: Unsigned value, 1 decimal place
Example: 123.4 stored as 1234
For 200 A < CT PRIMARY
≤
2000 A
Format: Unsigned value
Example: 1234 stored as 1234
For CT PRIMARY > 2000 A
Format: Unsigned value, scaled by 10
Example: 12340 stored as 1234
F84
16 bits
IRIG-B SIGNAL TYPE
0000 0000 0000 0000
0 = None
0000 0000 0000 0001
1 = DC Shift
0000 0000 0000 0010
2 = Amplitude Modulated
F85
16 bits
TRACE MEMORY TRIGGER CAUSE
0000 0000 0000 0000
0 = No Trigger
0000 0000 0000 0001
1 = Manual Trigger
0000 0000 0000 0010
2 = Automatic Trigger
F86
16 bits
VOLTS-PER-HERTZ CURVE
SHAPES
0000 0000 0000 0000
0 = Definite Time
0000 0000 0000 0001
1 = Inv Curve 1
0000 0000 0000 0010
2 = Inv Curve 2
0000 0000 0000 0011
3 = Inv Curve 3
Table 7–6: 745 DATA FORMATS (Sheet 21 of 25)
CODE
APPLICABLE BITS
DEFINITION
F87
16 bits
BLOCK SIGNAL
0000 0000 0000 0000
0 = Disabled
0000 0000 0000 0001
1 = Logic Input 1
0000 0000 0000 0010
2 = Logic Input 2
0000 0000 0000 0011
3 = Logic Input 3
0000 0000 0000 0100
4 = Logic Input 4
0000 0000 0000 0101
5 = Logic Input 5
0000 0000 0000 0110
6 = Logic Input 6
0000 0000 0000 0111
7 = Logic Input 7
0000 0000 0000 1000
8 = Logic Input 8
0000 0000 0000 1001
9 = Logic Input 9
0000 0000 0000 1010
10 = Logic Input 10
0000 0000 0000 1011
11 = Logic Input 11
0000 0000 0000 1100
12 = Logic Input 12
0000 0000 0000 1101
13 = Logic Input 13
0000 0000 0000 1110
14 = Logic Input 14
0000 0000 0000 1111
15 = Logic Input 15
0000 0000 0001 0000
16 = Logic Input 16
0000 0000 0001 0001
17 = Virtual Input 1
0000 0000 0001 0010
18 = Virtual Input 2
0000 0000 0001 0011
19 = Virtual Input 3
0000 0000 0001 0100
20 = Virtual Input 4
0000 0000 0001 0101
21 = Virtual Input 5
0000 0000 0001 0110
22 = Virtual Input 6
0000 0000 0001 0111
23 = Virtual Input 7
0000 0000 0001 1000
24 = Virtual Input 8
0000 0000 0001 1001
25 = Virtual Input 9
0000 0000 0001 1010
26 = Virtual Input 10
0000 0000 0001 1011
27 = Virtual Input 11
0000 0000 0001 1100
28 = Virtual Input 12
0000 0000 0001 1101
29 = Virtual Input 13
0000 0000 0001 1110
30 = Virtual Input 14
0000 0000 0001 1111
31 = Virtual Input 15
0000 0000 0010 0000
32 = Virtual Input 16
0000 0000 0010 0001
33 = Output Relay 1
0000 0000 0010 0010
34 = Output Relay 2
0000 0000 0010 0011
35 = Output Relay 3
0000 0000 0010 0100
36 = Output Relay 4
0000 0000 0010 0101
37 = Output Relay 5
0000 0000 0010 0110
38 = Output Relay 6
0000 0000 0010 0111
39 = Output Relay 7
0000 0000 0010 1000
40 = Output Relay 8
0000 0000 0010 1001
41 = Self-Test Relay
0000 0000 0010 1010
42 = Virtual Output 1
0000 0000 0010 1011
43 = Virtual Output 2
0000 0000 0010 1100
44 = Virtual Output 3
0000 0000 0010 1101
45 = Virtual Output 4
0000 0000 0010 1110
46 = Virtual Output 5
F88
16 bits
ASSERT SIGNAL
0000 0000 0000 0000
0 = Disabled
0000 0000 0000 0001
1 = Logic Input 1
0000 0000 0000 0010
2 = Logic Input 2
0000 0000 0000 0011
3 = Logic Input 3
0000 0000 0000 0100
4 = Logic Input 4
0000 0000 0000 0101
5 = Logic Input 5
0000 0000 0000 0110
6 = Logic Input 6
Table 7–6: 745 DATA FORMATS (Sheet 22 of 25)
CODE
APPLICABLE BITS
DEFINITION