Command Syntax
[SOURce:]VOLTage[:AC]:INITial
Description
This command is equivalent to the “[SOURce:]INITial <n>” command
but applies only to the AC1, AC2 and AC3 parameters.
VOLT:INIT? = ON Set points of the unit at power on will be the last set after power off.
The set points affected by this command are:
- Voltage AC1
- Voltage AC2
- Voltage AC3
VOLT:INIT? = OFF Set points of the unit at power on will have a default value of:
- Voltage AC1 = 0V
- Voltage AC2 = 0V
- Voltage AC3 = 0V
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b>
Example
VOLT:AC:INIT OFF
Query Format
[SOURce:]VOLTage[:AC]:INITial?
Returned Data Format
<b>
Query Example
VOLT:AC:INIT?
0
Command Syntax
[SOURce:]VPEAK:MARGin
Description
This command sets the over voltage protection trip level as an
absolute value. Thus, if the output voltage exceeds the programmed
v the Vpeak Margin, the OVP protection will trip off the
output and generate an OVP fault.
For example., if 230Vrms is programmed in AC mode and the Vpeak
margin is set to 20, the OVP will trip at 230 *
2 + 20 =345Vpeak.
Parameters
0.0 – 500.0
Parameter Format
<nr2>
Example
VPEAK:MARG 20.0
Query Format
[SOURce:]VPEAK:MARGin?
Returned Data Format
<nr2>
Query Example
VPEAK:MARG?
20.0000